5.4 Configuration with Power Conversion Devices
AES batteries must be set up to work with the Power Conversion devices in either an Open Loop or Closed Loop
configuration. The charge and discharge settings in a Open Loop configuration are set up through the controller for the
Power Conversion device at the time of installation. In a Closed Loop configuration, charge and discharge settings are
dynamically controlled by the BMS of the AES Battery over a connection with the Power Conversion device network. Closed
Loop communication with a Power Conversion device network requires the use of a LYNK Gateway Communication device
(p/n 950-0015) available from Discover Battery.
For Closed Loop and Open Loop configuration details please refer to the appropriate Application Note for your Power
Conversion device available from the Discoverbattery.com website, or contact your Discover Battery provider for assistance.
6. Operation
6.1 On–Off / Reset
• To set the battery to ON press and hold switch for 2-3 seconds
• To set the battery to OFF press and hold switch for 2-3 seconds
6.2 Charging
Before operating the charger make sure to read and understand the instructions that come with the charger. Never attempt to
charge a battery without first reviewing and understanding the instructions for the charger being used.
1. Connect the Power Conversion device's charger leads to the battery.
2. Ensure the charger and battery side connections are tight.
3. Set the charger to ON
4. Set the battery to ON
Spikes are fast, short duration electrical transients in voltage (voltage spikes), current (current spikes), or transferred energy
(energy spikes) in an electrical circuit. Voltage spikes usually happen when the AC/DC adaptor is plugged in, or charge current is
cut off quickly. Multi voltage chargers are constructed using transformers that may be capable of producing spikes that exceed
the maximum ratings of the Discover AES Battery. You must ensure that the charger being supplied:
• Meets the recommended charge curve
• Incapable of exceeding Discover's maximum terminal voltages
Review operating limits.
Always make sure the chargers charging curve meets the battery's
charging requirement; never charge a visibly damaged battery; never
charge a frozen battery.
NOT ALL CHARGERS ARE CAPABLE OF CHARGING LITHIUM BATTERIES
CONFIRM that your chosen charger is incapable of producing transient
spikes that exceed the published terminal voltage limits for the battery.
▲ NOTE!
▲ CAUTION!
▲ CAUTION!