RECEIVER OPTION SELECTOR
OPTION 1 - CLASS 2
ON
Class 2 enabled. Standard setting for safety operation.
OFF
Class 2 disabled
OPTION 2 - TRANSMITTER FRECUENCY
ON
Frequency 869,85 MHz
OFF
Frequency 868,95 MHz
OPTION 3 - RECEIVER TEST TYPE
ON
Normally Open contact
OFF
Normally Close contact
OPTION 4 - AUTOMATIC FRECUENCY AGILITY
ON
Automatic frequency Agility enabled
OFF
Automatic frequency Agility disabled
CLASS 2:
- It is very important that the selected frequency coincides with the
transmitter. Otherwise the system will not work.
- With class 2 Disabled the current consumption is less. this is the
perfect setting for storing the product (5uA class 2 disabled to 15uA
class 2 enabled).
- Every 5 seconds there is a transmission.
- If no signal is received during 15 seconds, receiver relays goes to
security
- Receiver test only checks the relay.
- Receiver will not work until all programmed transmitters are identified.
TERMINAL CONNECTIONS
1 2 3
TRANSMITTER
8K2
RESISTIVE
SAFETY
EDGE
1 2 3 4 5 6 7
RECEIVER
12/24V
AC/DC
Instruction Manual
GENERAL (RECEIVER)
Important:
- To replace transmitter battery and safety of the power supply insert battery 1 first and then battery 2! Unless this order is observed, correct
function is not guaranteed. Batteries must be suitable for use at temperatures of -20°C and above.
- System has no fuse protection. It is advisable to include a fuse protection of minimum 100mA and maximum 250mA into the external power.
PROGRAMMING PROCESS
CODE MEMORIZATION
-
Press button PROG button for 1,5 sec.
-
On hearing the acoustic signal stop pressing as the receiver will be logged into the memorizing code process
-
From this moment received transmitters will be memorized.
-
In order to memorize push PROG button on the transmitter.
-
The memorization of a code is acknowlegde with one acoustic signal.
-
The receiver will exit from memorization code process automatically after 10 seconds from the last transmitter input. This will be indicated
with two acoustic signals.
MEMORY RESET
-
Press PROG button for 3,5 seconds.
-
After 1,5 seconds one acoustic signal will be heard indicating that you have entered the code memorization mode, maintain the button
pressed.
-
After 3,5 seconds you will hear several acoustic signals for 10 secs.
-
Stop pressing the button.
-
The WirelessBand will have reset all transmitters.
-
The System remains in memorization process, ready to receive new transmitters
MEMORY FULL INDICATOR
In case of full memory you will hear several acoustic signals for 10 seconds upon trying to memorize a new transmitter.
LOW BATTERY INDICATOR
Low battery indication consists on 4 acoustic sounds each time a message is received from a programmed transmitter. Both, warning LED and buzzer are
set on simultaneously.
INHIBITOR
WARNING!!
- Installation, startup, modification and retrofitting of the system may only be carried out by an electrician.
- Switch off the operating voltage before working on the system.
- The control unit may only be used to protect against dangers at crushing and shearing points on automatic sliding gates
(designated Use). Any other use is prohibited.
8K2
OUTPUT
RELAY
NC NO
TEST
( WIRELESSBAND 1.0 )