Mounting Instructions

Select a suitable mounting spot on an exterior wall where the sensor is best protected from direct exposure to sunlight, wind, etc.
preferably on a north-facing wall. Do not mount the sensor near opening windows, supply/exhaust air louvres or other known air
disturbances. Avoid areas where the sensor is exposed to vibrations or rapid temperature changes.
The humidity/temperature transmitter enclosure provides a connection hole for 1/2" Conduit. Run a length of conduit through exterior
wall and seal. Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring
used to supply inductive loads such as motors. Make all connections in accordance with national and local codes.
The humidity/temperature transmitter installs directly on an exterior wall using the two integrated mounting holes provided on the
enclosure. Select the best mounting technique based on the exterior wall material. The two mounting holes will facilitate a #10 size
screw (not supplied). The sensor fitting must be pointing down. See Figure 2.
Figure 2: Mounting
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch on the right side of the enclosure, while
simultaneously pulling on the cover, as shown on Figure 3.
Figure 3: Opening
Feed conduit through the provided hole in the back of enclosure and secure with a lock nut as shown in Figure 4. It is recommended
that weatherproof conduit or cable gland fittings be used.