Cameron Demco Руководство по установке, эксплуатации и техническому обслуживанию - Страница 10
Просмотреть онлайн или скачать pdf Руководство по установке, эксплуатации и техническому обслуживанию для Блок управления Cameron Demco. Cameron Demco 11 страниц. Resilient-seated butterfly valve
WORM GEAR OPERATED
Worm gear operators are recommended for valves larger than 6 inches. Clockwise rotation of the handwheel
closes the butterfly valve. Counterclockwise rotation opens the valve.
Gear operators are always mounted with the input shaft perpendicular to the pipe axis for handwheel clearance.
Each operator has an arrow on the top of the gear, which indicates the "OPEN - CLOSED" position of the valve
(Figure 13).
AUTOMATIC VALVES
Butterfly valves with their quarter turn operation are easily adapted to automatic actuators for remote operation.
To prevent water hammer, actuators should close the valve slower than 6 to 8 seconds, open-to-close. Rapid
closure causes water hammer which can break or otherwise damage valve parts.
MAINTANENCE PROCEDURES
TROUBLESHOOTING
Trouble
The valve will not seal
Foreign matter is present between seat
properly.
Operator stops are not set properly.
Build-up of solids or roughness on edge
The valve is hard to
operate.
TC-003001-01 / Rev 2
CLOSED
Figure 12 – Valve with Gear Operator
Table 6 - Troubleshooting
Probable Cause
The seat and/or disc is worn or
damaged.
and disc.
of disc.
Operator is not installed properly.
OPEN
CLOSED
Replace worn parts.*
Operate several times to wipe clean.
Adjust stops to proper setting.
Operate several times to wipe clean or disassemble valve
and clean disc edge.*
Reinstall operator in proper alignment with valve stem.
10