Camille Bauer SIRAX CT100 Инструкции по безопасности - Страница 3
Просмотреть онлайн или скачать pdf Инструкции по безопасности для Трансформатор Camille Bauer SIRAX CT100. Camille Bauer SIRAX CT100 4 страницы. Wound primary current transformer
Wound primary Current Transformer SIRAX CT100 / CT110
Safety instructions
The unobjectionable and hazard-free operation presupposes that the
safety instructions as well as Device Manual, electronically down-
loadable via www.camillebauer.com, have been read and understood.
The installation and commissioning should only be carried out by trained
personnel.
Check the following points before commissioning:
- that the connection wires are not damaged, and that they are not live during
wiring
- that the power flow direction and the phase rotation are correct
The instrument must be taken out of service if safe operation is no longer pos-
sible (e.g. visible damage). In this case, all the connections must be switched
off. The instrument must be returned to the factory or to an authorized service
dealer.
It is forbidden to open the housing and to make modifications to the instrument.
The instrument is not equipped with an integrated circuit breaker. During instal-
lation check that a labeled switch is installed and that it can easily be reached
by the operators.
The device is maintenance free. Unauthorized repair or alteration of the unit
invalidates the warranty.
Application area
Wound primary current transformers are used wherever small primary
rated currents of 1 A or more must be converted by the measuring system
into usable, galvanically isolated secondary rated currents of 5 A or 1 A.
The primary current as well as the secondary current is connected directly
via screw terminals on the order and rear side.
Mounting and installation
Ensure a safe working environment during assembly, installation
and maintenance work. Disconnect the power supply of the
primary conductor and secure it against unintentional reconnec-
tion.
• The installation of the devices is arbitrary.
• Connect the primary current according to the connection diagram to the
provided screw terminals. Note the marking of the primary terminals.
• The installation of the current transformers is carried out on a mounting
plate using a foot mounting bracket. To do this, use the fastening aids
supplied.
• Connect now the secondary connections according to the connection
diagram. Observe the marking of the secondary terminals.
Electrical connections
Attention: Danger to life! Ensure that all leads are free of potential
when connecting them!
Please observe that the data on the type plate must be adhered to !
The national provisions have to be observed in the installation and
material selection of electric lines!
P1
(K)
S1
S2
(k)
(I)
A
P2
(L)
k-S1
I-S2
L
K-P1
L-P2
N
Technical data
Input
Primary current I
Dynamic short circuit current I
Thermal short circuit current I
Thermal rated current I
Nominal frequncy
Output
Secondary current I
Class of accuracy
Rated burden S
Instrument security factor FS
Environmental conditions
Ambient temperature
Storage temperature
Relative humidity (without condensation)
Operating height
Safety
Overvoltage category
Degree of pollution
Test voltage
Rated insulation level
Insulation class
Body protection IP
Mechanical properties
Housing material
Flammability class
Connections
Connection technology Primary and
Secondary conductor
Connection cross-section secondary
conductor
Tightening torque
Standards
Standards accepted
Sign explanation
RL
pr
dyn
th
cth
sr
r
UL94 V-0, self-extinguishing, non-dripping,
M4 screws with self lifting clamp strap
max. 4 mm2 with wire end ferrule; 6 mm2
Device may only be disposed of in a professional manner
Attention: Danger to life!
Please note
Caution! General hazard point. Read the operating instructions.
This product was developed and manufactured in accordance with
the applicable regulations (IEC 61010, IEC 61869) and meets the
requirements of the low voltage guideline 2006/95/EG
Please refer to our operating instructions for details. Downloadable
from our website www.camillebauer.com
1 ... 60 A
2.5 x I
th
40 x I
pr
1.0 x I
(100%)
pr
50 ... 60 Hz
5 A or 1 A
0.2; 0.5
1 ... 5 VA
FS10; FS15
-20 ... +45 °C
-50 ... +80 °C
5 ... 85 %
2000 m
III
2
3 kV; 50 Hz; 1 min
0.72 kV
E (120 °C)
IP20
Polycarbonate
halogen-free
solid
max. 2 Nm
IEC 61869-1; IEC 61869-2
3