esera automation Multisensor Pro I Руководство пользователя - Страница 3
Просмотреть онлайн или скачать pdf Руководство пользователя для Аксессуары esera automation Multisensor Pro I. esera automation Multisensor Pro I 8 страниц. 1-wire sensor for temperature, humidity and air quality w/auto-e-connect
Art. No. 11151
6
Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, Fault-free operation
EN 61000-6-3, Stray radiation
RoHS
7
LED Display
The "LED traffic light" switches off approx. 800ppm from green to yellow and from approx. 1200ppm to red. The
switching thresholds of the LED display are permanently programmed.
You can permanently activate the "night function" of the traffic light function by long pressing of the calibration
button on the device connection side. In the delivery state, the night function for the traffic light LED is not active,
which means that the traffic light LED illuminates independently of the ambient brightness.
If the night function is activated, the LED display is switched off by an internal light sensor during darkness in
order to be able to sleep undisturbed during the night, for example. The light sensor is only intended for
brightness control of the LEDs and cannot be read out externally.
All sensor functions remain in operation even when the LEDs are switched off. When mounting, make sure that
the sensor is not darkened, otherwise the LED display may be permanently off.
Table 7.1:
LED
Function
green
Lights up for CO2
<800ppm
Good air conditions
yellow
-
Initial commissioning:
CO2 >
Flashes during the start phase
800ppm
for approx. 2 hours.
-
Operation:
Sufficient air conditions
red
-
Commissioning:
CO2 >
Flashes during the start phase
1200ppm
for approx. 15 hours.
-
Operation:
LED flashes, poor air
conditions.
8
Commissioning and warm-up
A calibration of the temperature and humidity sensor is not necessary. The air quality sensor is pre-
calibrated.
After applying the supply voltage, the integrated sensor controller checks the warm-up time after which the
air quality sensor starts. The three possible stages of the warm-up phases are indicated by the three LEDs
on the front.
It is normal for the 1-Wire air quality sensor to require a "warm-up time" after connecting the supply voltage.
During commissioning, the integrated sensor controller checks which warm-up stage the sensor starts with.
The three possible stages of the warm-up phases are indicated by the three LEDs on the front.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
Designation
-
If the power supply was only briefly interrupted, the
sensor starts normal operation directly without
warm-up time.
-
The LED illuminates in good air conditions up to
approx. 800 ppm CO2 in the air.
-
The LED flashes as a sign of the start phase.
-
The 1-Wire interface constantly outputs 0 ppm of the
air quality value.
-
After the warm-up time, the sensor switches to
normal operation.
-
The LED flashes as a sign of the start phase.
-
The 1-Wire interface constantly outputs 0 ppm of the
air quality value.
-
After the warm-up time, the sensor switches to
normal operation.
11151 V2.0 R1.0 Manual
Page 3 of 8