esera automation 11228 V2 Руководство пользователя - Страница 4

Просмотреть онлайн или скачать pdf Руководство пользователя для Системы ввода/вывода esera automation 11228 V2. esera automation 11228 V2 7 страниц. 8-fold high power switching module / binary output w/auto-e-connect

esera automation 11228 V2 Руководство пользователя
7
Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, fault-free operation
EN 61000-6-3, stray radiations
RoHS
8
Operating mode, display and operation
The module has two operating modes: Normal mode and manual mode.
Normal operation: After commissioning, the device is in normal operation, which means that a switching
command via the 1-wire interface is switched directly to the corresponding output relay. The corresponding output
LED lights up.
Manual mode: By pressing the "MAN/Select" key for 2 seconds, the module switches to manual mode (manual
mode). The "PWR" LED flashes as confirmation.
Press the "MAN/Select" button briefly to select an output. The LEDs 1-8 light up for the selected output. Press the
"ON/OFF" key to switch the selected output on or off.
Several outputs can be switched in one cycle.
After a waiting time of approx. 2 seconds, the system automatically switches to "normal operation" mode, the
"PWR" LED lights up permanently again, and the selected outputs are activated.
Delete "Manual mode": By pressing the "ON/OFF" key for 2 seconds, the outputs selected in manual mode are
switched off.
Display
Description
LED 1-8
Output 1-8
LED PWR
Power
LED Status
Status display
manual mode
Pushbutton Description
MAN/Select
Operating mode /
channel selection
ON/OFF
Output 2 On/Off
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
Function LED display
- LED lights up for 2 seconds to start the system
- Normal operation: LED indicator lights up when the output is
active
- Manual operation: The "Select" button can be used to select the
output that is switched on or off.
- LED lights up 2 seconds to start the system
- LED indicator lights up when an output relay is active
- LED display flashes in manual mode
- LED lights up for 2 seconds to start the system
- Status display of the selected output after transition to normal
operation (relay on or off)
Function pushbutton
The pushbutton has two functions
- Switch to manual mode (press for 2 seconds)
- Output selection (press briefly)
The pushbutton has two functions
- Selected output On - Off (press briefly)
- Delete all manual mode outputs (press for 2 seconds)
11228 V2.0 R1.0 Manual
Page 4 of 7