Unit weights
Before rigging any BAC equipment, the weight of each section should be verified on the unit certified drawing.
Refer to the Rigging section for weight values.
These weights are approximate only and should be confirmed by weighing before lifting when available
hoisting capacity provides little margin for safety.
Model - TSU-M
TSU-237M
TSU-476M
TSU-594M
TSU-761M
TSU-L184M
TSU-L370M
TSU-L462M
TSU-L592M
Approximate shipping weights TSU-M
Before an actual lift is undertaken, ensure no water, snow, ice or debris has collected in the unit.
Such accumulations will add substantially to the equipment's lifting weight.
Leveling
The unit must be level for proper operation and ease of piping.
The unit MUST be installed on a concrete slap with a levelness or maximum slope of 2 mm per meter and the
flatness should be no more than 6 mm over a 3 meter span.
Support beams must also be level as shims should not be used between pan and support beams to level the unit.
Connecting pipework
All piping external to BAC cooling equipment must be supported separately.
In case the equipment is installed on vibration rails or springs, the piping must contain compensators to eliminate
vibrations carried through the external pipework.
All connections in the external pipework (installed by others) must be leak free and tested accordingly.
1 General information
1 General information
Approx. shipping weight (kg)
CAUTION
4420
7590
9150
10990
3760
6400
7710
9200