10.3 ALARM RECOVERY
Probe alarm: "P1" (probe1 faulty), automatically stops 10s after the probe restarts normal operation.
Check connections before replacing the probe.
Temperature alarms "HA" and "LA" automatically stop as soon as the thermostat temperature returns
to normal values.
Door switch alarm "dA" stop as soon as the door is closed.
External alarms "EAL", "BAL" stop as soon as the external digital input is disabled
Pressure switch alarm "PAL" alarm is recovered by switching OFF the instrument.
11. TECHNICAL DATA
Housing: self extinguishing ABS.
Case
XW10L: facia 38x185 mm; depth 76mm
XW10V: facia 100x64 mm; depth 76mm
Mounting
XW10L: panel mounting in a 150x31 mm panel cut-out with two screws.
between the holes 165mm
XW10L: panel mounting in a 56x72 mm panel cut-out with two screws.
between the holes 40mm
Protection: IP20.
Frontal protection: IP65 with optional frontal gasket mod RG-L (XW40L); RGW-V (XW40V).
Connections: Screw terminal block
2,5 mm
Power supply: 230Vac or. 110Vac
10%
±
Power absorption: 7VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 1 NTC or PTC probe
Digital input: 1 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac or. SPST 8(3) A, 250Vac
light: XW10L: relè SPDT 8(3) A, 250Vac; XW10V: relè SPST 16(6) A, 250Vac
Other output : alarm buzzer (optional)
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20
85% (no condensing)
÷
Measuring and regulation range:
PTC probe: -50÷150°C (-58÷302°F)
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
12. CONNECTIONS
16A
250Vac
2 3 4
Light
8A
20A
250Vac
250Vac
1 2 3 4
5 6 7 8 9 10 11
Luce
Comp
1592009211 XW10L-V GB r1.0 30.05.2011
3 x 2mm. Distance
3x2mm. Distance
2
heat-resistant wiring and 6,3mm Faston
Room
Digital
Probe
Input
17 18
19
20 21
XW10V
20A
250Vac
MAX
20A
5 6 7 8 9 10 11
12
Comp
XW10L
MAX
20A
12
13 14 15 16
17
Room
Probe
13. DEFAULT SETTING VALUES
Label Name
REGULATION
Set
Set point
Hy
Differential
LS
Minimum set point
US
Maximum set point
OdS
Outputs activation delay at start up
AC
Anti-short cycle delay
CCt
Compressor ON time during fast freezing
COn
Compressor ON time with faulty probe
COF
Compressor OFF time with faulty probe
CH
Type of regulation
DISPLAY
CF
Temperature measurement unit
rES
Resolution (integer/decimal point)
ALARMS
ALC
Temperature alarms configuration
ALU
MAXIMUM temperature alarm
ALL
minimum temperature alarm
AFH
Temperature alarm differential
ALd
Temperature alarm delay
dAO
Delay of temperature alarm at start up
dot
Delay of temperature alarm after closing the
door
dOA
Open door alarm delay
nPS
Pressure switch number
ANALOGUE INPUTS
Ot
Thermostat probe calibration
HES
Temperature increasing during the Energy
Saving cycle
DIGITAL INPUTS
Odc
Open door control
I2P
Configurable digital input polarity
i2F
Digital input configuration
dId
Digital input alarm delay
OTHER
Pbc
Kind of probe
rEL
Software release
Ptb
Map code
Prd
Probes display
Pr2
Access parameter list
XW10L – XW10V
Range
Default
Level
°C/°F
LS÷US
5/41
Pr1
0,1÷25,5 °C / 1÷45°F
2/4
Pr1
-50,0°C÷SET / -58°F÷SET -50/-58
Pr2
SET ÷ 110°C / SET ÷
110/230
Pr2
230°F
0÷255 min.
0
Pr2
0÷30 min.
1
Pr1
0 ÷ 23h 50 min.
0.0
Pr2
0÷255 min.
15
Pr2
0÷255 min.
30
Pr2
CL, Ht
CL
Pr2
°C ÷ °F
°C/F
Pr2
in ÷ de
dE/-
Pr1
rE÷Ab
Ab
Pr2
-50,0÷110°C/ -58÷230°F
110/230
Pr1
-50,0÷110°C/ -58÷230°F
-40/-40
Pr1
0,1÷25,5 °C / 1÷45°F
2/4
Pr2
0÷255 min.
15
Pr2
0 ÷ 23h 50 min.
1,3
Pr2
0÷255 min.
15
Pr2
0÷255 min.
15
Pr2
0÷15
0
Pr2
-12,0÷12,0°C / -21÷21°F
0/0
Pr1
-30÷30°F/-54÷54°F
0/0
Pr2
no, Fan, CPr, F_C
no
Pr2
CL÷OP
CL
Pr2
dor, EAL, bAL, PAL, dFr,
dor
Pr2
AUS, ES, OnF
0÷255 min.
5
Pr2
PbC, ntc
ntc/Ptc
Pr2
- - -
2.0
Pr2
- - -
- - -
Pr2
Pb1
- - -
Pr2
- - -
- - -
Pr1
4/4