The following table describes the default parameters:
Label
Description
SEt
Set point
Hy
Differential
odr
Regulation offset
Temperature increase during energy
HES
saving cycle
CH
Kind of action: heating cooling
rPA
Regulation probe A
rPb
Regulation probe B
rPE
Virtual probe percentage
CF
Measurement units
odS
Start up outputs delay
rHC
Humidity probe presence
orH
Humidity probe calibration
tdC
Internal probe temperature presence
ot
Internal probe temperature calibration
AuC
External temperature probe presence
oE
External temperature probe calibration
AOC
Analog output configuration
Ant
Analog output action: direct or inverse
LAo
Lower input limit for analog output value
uAo
Upper input limit for analog output value
oAL
Minimum analog output percentage
oAU
Maximum analog output percentage
MANUAL MODE: Analog output
An
percentage
Analog output percentage during probe
oAE
error
rLS
Relay presence
rLC
Relay configuration
Ltr
Lower trimmer offset (Only for XH55P)
Utr
Upper trimmer offset (Only for XH55P)
tAr
PWM cycle (Period)
1592030000 xh50_55p r1.2 gb 2011.06.28.doc
LrL
Minimum PWM percentage
Range
Value
urL
Maximum PWM percentage
[-40.0°C ÷ 80.0°C]
MANUAL MODE: Relay output
18.0
rOP
[-40°F ÷ 176°F]
percentage
[0.1°C ÷ 25.5°C]
Relay output percentage during probe
5.0
rLO
[1°F ÷ 45°F]
error
[-12.0°C ÷ 12.0°C]
1.0
ALP
Probe selection for temperature alarms
[-21°F ÷ 21°F]
[-20.0°C ÷ 20.0°C]
0.0
ALL
Minimum temperature alarm
[-36°F ÷ 36°F]
dir(0); ind(1)
ind
ALU
Maximum temperature alarm
nP(0); Etr(1); int(2)
ext
Differential for temperature alarm
nP(0); Etr(1); int(2)
nP
AFH
recovery
0 ÷ 100%
100
ALd
Temperature alarm delay
°C(0); °F(1)
°C
dAo
Delay of temperature alarm at start up
0 ÷ 255 sec
0
diS
Digital input presence
no(0); YES(1)
YES
idF
Digital input configuration
-10 ÷ 10 %HR
0
idd
Digital input delay
no(0); YES(1)
YES
rEL
Software release
[-12.0°C ÷ 12.0°C]
0.0
Ptb
Map code
[-21°F ÷ 21°F]
no(0); YES(1)
YES
16. TECHNICAL DATA
[-12.0°C ÷ 12.0°C]
0.0
[-21°F ÷ 21°F]
Case: for box 503 and wall mounting. 80x120x25.6mm
nP(0); Etr(1); int(2);
Connections: screw terminal blocks 2.5mm
HPr( 3); dP(4); dEP(5);
HPr
Power supply: 12 ÷ 24Vac or 12 ÷ 40Vdc
MAn(6)
Power absorption: 3VA max
dir(0); in (1)
dir
NTC input: 10Kohm@25°C
[-40.0°C ÷ uAO]
Digital input: free of voltage
[-40°F ÷ uAO]
0
Outputs: 8A SPDT (16A SPDT optional)
[0% ÷ uAO]
0÷10Vdc output impedance 47 ohm 10mA maximum
[LAo ÷ 80.0°C]
Measuring and regulation range: Humidity 1 ÷ 99% R.H. 3.5%
[LAo ÷ 176°F]
100
[LAo ÷ 100%]
Operating temperature: -10 ÷ 60°C
0% ÷ oAU
0
Storing temperature: -25 ÷ 60°C
Data storing: on the non-volatile memory (FLASH)
oAL÷ 100%
100
Pollution degree: normal
0 ÷ 100%
0
Software class: A
Rated impulsive voltage: 2500V
0 ÷ 100%
0
no(0); YES(1)
YES
nP(0); Mod(1); dEP(2);
dEP
tEr(3); MAn(4)
[-12.0°C ÷ Utr]
-3.0
[-21°F ÷ Utr]
[Ltr ÷ 12.0°C]
3.0
[Ltr ÷ 21°F]
10 ÷ 255 min
10
0% ÷ urL
0
LrL ÷ 100%
100
0 ÷ 100%
0
0 ÷ 100%
80
nP(0); Etr(1); int(2);
nP
TEq(3)
[-40.0°C ÷ ALU]
-40.0
[-40°F ÷ ALU]
[ALL ÷ 80.0°C]
80.0
[ALL ÷ 176°F]
[0.1°C ÷ 25.5°C]
1.0
[1°F ÷ 45°F]
0 ÷ 255 min
0
0 ÷ 255 min
0
no(0); YES(1)
YES
En(0); ES(1); inA(2)
En
0 ÷ 60sec
0
sola lettura
1.1
sola lettura
1
2
Temperature -40 ÷ 80°C (-40 ÷ 176°F)
XH50-55P
5/5