Arthur Grillo DPC200-AC Руководство по установке и эксплуатации - Страница 12

Просмотреть онлайн или скачать pdf Руководство по установке и эксплуатации для Контроллер Arthur Grillo DPC200-AC. Arthur Grillo DPC200-AC 16 страниц. Differential pressure controller

Arthur Grillo DPC200-AC Руководство по установке и эксплуатации
OPERATION
fan k-factor
k = 70

5.5 Adjustable parameters

Parameter
Unit
Metric or imperial
Operating
Measuring mode or control mode
mode:
Differential pressure ΔP [Pa] or [InH
Parameter
Volume flow V [m
Volume flow calculation according to: V = k · √Δp
with: V = Volume flow in [m
Volume flow range up to 999,999 m
K-factor:
Maximum volume flow (V
Measuring range:
Measuring range: 500 Pa, k=10,000
Measuring range: 1000 Pa, k=10,000
Measuring range: 2000 Pa, k=10,000
Measuring range: 4000 Pa, k=10,000
Measuring range: 6000 Pa, k=10,000
Differential pressure from 0 % up to 100 % of measuring range.
Limit values:
Volume flow from 0.5 % up to 100 % of measuring range, k-factor is
considered.
Nominal
Differential pressure from 0 % up to 100 % of measuring range.
values
Volume flow from 0.5 % up to 100 % of measuring range, k-factor is
(setpoints):
considered.
Output
0...10 V DC
voltage:
P-gain:
0...1000
I-gain:
0...100
positive/(heating): Control deviation = set value – actual value
Control
The output increases when: Set value > actual value
characteri-
negative/(cooling): Control deviation = actual value – set value
stic:
The output increases when: Actual value > set value
12
If selected parameter = volume flow
than follows the additional input for the k-factor
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Selection or parameter range
/h or cfm]
3
k = flow factor, adjustment range: 1...10,000
Δp = differential pressure in [Pa] or [InH
50 Pa, k=10,000
Doc.-no.: DPC200-AC_01_EN
O]
2
/h] or [cfm]
3
O]
2
/h
3
)
max
V
= 70,710 m
max
V
= 223,607 m
max
V
= 316,228 m
max
V
= 447,214 m
max
V
= 632,456 m
max
V
= 774,597 m
max
Issue: 07/2019
Default setting
metric
measuring mode
differential
pressure ΔP [Pa]
K = 70
/h;
3
/h;
3
/h;
3
/h;
3
/h;
3
/h
3
placeholder
1: 8888
2: 8888
U
= 10 V DC
out
P = 50
I = 3.15
positive / heating
OFF