Arthur Grillo DPC200-MOD Руководство по установке и эксплуатации - Страница 11
Просмотреть онлайн или скачать pdf Руководство по установке и эксплуатации для Контроллер Arthur Grillo DPC200-MOD. Arthur Grillo DPC200-MOD 18 страниц. Differential pressure / volume flow controller
5.5 Control mode
Display
controlling mode
ΔP = 150 Pa
menu
modbus
unit metric
operating mode
control mode
parameter
diff. pressure
setpoint
50 Pa
output voltage
U = 10.0 V DC
P - parameter
50
l - parameter
3.15
controlling mode
positive / heating
back and confirm
Doc.-no.: DPC200-MOD_02_EN
Start menu: Press button B1 approx. two seconds
Press button B2 to get to the next menu item
Press button B1 to switch between:
on <=> off
Press button B2 to get to the next menu item
Press button B1 to switch between:
metric <=> imperial
Press button B2 to get to the next menu item
Press button B1 to switch between:
measuring mode <=> control mode
Press button B2 to get to the next menu item
Press button B1 to switch between:
diff. pressure <=> volume flow
Press button B2 to get to the next menu item
If selected parameter = diff. pressure
Button B1: reset value
Button B2: set value
Button B1: confirm value, display flashes once
Press button B2 to get to the next menu item
Button B1: reset value
Button B2: set value
Button B1: confirm value, display flashes once
Press button B2 to get to the next menu item
Button B1: reset value
Button B2: set value
Button B1: confirm value, display flashes once
Press button B2 to get to the next menu item
Button B1: reset value
Button B2: set value
Button B1: confirm value, display flashes once
Press button B2 to get to the next menu item
Press button B1 to switch between:
positive / heating <=> negative / cooling
Press button B2 to go to the next menu
Press button B1 to leave the menu
Press button B2 to stay in the menu
Action
Issue: 08/2019
OPERATION
11