Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all
local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in
the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the
enclosure's upper keyholes over the two upper screws, level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure's
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all
screws (Enclosure Dimensions, pg. 12). Secure enclosure to earth ground.
It is recommended to first review the following tables to facilitate installation:
Output Voltage and Stand-by Specifications Charts
Typical Application Diagram
LED Diagnostics
Terminal Identification Tables
Hook-up Diagrams
2. Set output voltage:
AL400ACM220 and AL600ACM220: set desired DC output voltage by setting switch SW1 to the
appropriate position on the power supply board. AL1012ACM220 is factory set at 12VDC and
AL1024ACM220 is factory set at 24VDC (Output Voltage and Stand-by Specification Charts below).
Output Voltage and Stand-by Specification Charts:
AL400ACM220
Voltage
Switch Position
12VDC
SW1 - ON
24VDC
SW1 - OFF
AL600ACM220
Voltage
Switch Position
12VDC
SW1 - ON
24VDC
SW1 - OFF
AL1012ACM220
Voltage
Switch Position
12VDC
N/A
AL1024ACM220 (refer to AL1024ACM220 Battery Size Calculation Worksheet, pg. 10).
Stand-by
Voltage
Battery
24VDC
12AH
24VDC
65AH
3. Connect AC (Fig. 2, pg. 7):
Connect unswitched AC power (220VAC, 50/60Hz) to terminals marked [L, N].
Use 14 AWG or larger for all power connections. Secure green wire lead to ground lug.
Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input,
Battery Wires). Minimum 0.25" spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside.
Refer installation and servicing to qualified service personnel.
4. Measure voltage before connecting devices. This helps avoiding potential damage.
ACM220 Series Installation Guide
Installation Instructions:
Stand-by Battery
40AH
40AH
Stand-by Battery
40AH
40AH
Stand-by Battery
40AH
15 mins. Stand-by /
5 mins. Alarm
7.7A / 9.7A
–
(pg. 3)
(pg. 6)
(pg. 6)
(pg. 5)
(pg. 8-9)
4 hr. Stand-by /
5 mins. Alarm
3.5A / 3.5A
2.75A / 2.75A
4 hr. Stand-by /
5 mins. Alarm
5.5A / 5.5A
5.75A / 5.75A
4 hr. Stand-by /
5 mins. Alarm
9.5A / 9.5A
4 hr. Stand-by /
5 mins. Alarm
1.2A / 9.7A
7.7A / 9.7A
24 hr. Stand-by /
5 mins. Alarm
24 hr. Stand-by /
5 mins. Alarm
24 hr. Stand-by /
5 mins. Alarm
24 hr. Stand-by /
5 mins. Alarm
–
1.2A / 9.7A
1A / 3.5A
1A / 3A
0.5A / 5.5A
0.75A / 5.75A
0.5A / 9.5A
60 hr. Stand-by /
5 mins. Alarm
–
200mA / 9.7A