Altronix AL1002ADA220 Руководство по применению - Страница 5

Просмотреть онлайн или скачать pdf Руководство по применению для Удлинитель Altronix AL1002ADA220. Altronix AL1002ADA220 8 страниц. Nac power extender
Также для Altronix AL1002ADA220: Руководство по установке (17 страниц)

Altronix AL1002ADA220 Руководство по применению
Outputs must be programmed independently (OUT1 - OUT4)
Function
Input to Output
Follower Mode
Temporal Code 3 Mode
Steady Mode
For the above modes DIP Switch 4 determines which Input controls the
corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Function
Amseco
Sync Mode*
®
Gentex
Sync Mode*
Gentex is a registered
trademark of
Gentex Corporation.
®
System Sensor
Sync Mode*
System Sensor is a
registered trademark
of Honeywell.
®
CooperWheelock
Sync Mode*
CooperWheelock is a
registered trademark
of Cooper Wheelock.
*Note: AL602ADA220, AL802ADA220 and AL1002ADA220 will only synchronize horns, horn/strobes and
strobes that contain synchronization capability. The same synchronization mode must be selected for all outputs.
02 ADA220 Application Guide
Output Programming Selection Table:
Switch Positions
ON
OFF
1
2, 3
3
1, 2
1, 2, 3
Sync Mode Selection Table:
Switch Positions
ON
OFF
1, 3,
2
4
1, 2,
3, 4
1, 2, 4
3
2, 3, 4
1
Descriptions
Output follows signal it receives from the corresponding
input (i.e. FACP Sync module - maintains synchronization of
notification appliance circuit).
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
This mode will accept steady or pulsing input.
Descriptions
This mode is designed to work with the Amseco series of horns,
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and allowing audible notification appliances (horns) and
visual notification appliances (strobes) to be silienced/ deactivated
at the same time.
This mode is designed to work with the Gentex
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and allowing audible notification appliances (horns) and
visual notification appliances (strobes) to be silienced/ deactivated
at the same time.
This mode is designed to work with the System Sensor
horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash
timing of the strobe, and allowing audible notification appliances
(horns) and visual notification appliances (strobes) to be silienced/
deactivated at the same time.
This mode is designed to work with the CooperWheelock series of
horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash
timing of the strobe, and allowing audible notification appliances
(horns) and visual notification appliances (strobes) to be silienced/
deactivated at the same time.
AL800LGK9E Board
Output DIP Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
®
series of horns,
®
series of
- 5 -