7.3.4 Energize the loop. The standby mode will be set in 10 sec. The left indicator 
on Rx shall pulse every second with low brightness. 
7.3.5  Place    the  1  dB  optical  attenuator  for  at  least  15  sec    in  the  in  immediate 
proximity (not greater than 2 cm) to the optical system window of the receiver so that the 
optical  axe  of  Rx  lens  mates  the  attenuator's  center.  The  detector  shall  remain  in  the 
standby mode.  
7.3.6 Remove the 1 dB optical attenuator and in the same way set the 2 dB optical 
attenuator.   The detector will go to the pre‐alarm mode, with both indicators flashing on 
the receiver once every 1 sec 5 times. The brightness of the left indicators flashes will be 
lower than those of the right one. After that the detector will go to the fire mode.  
7.3.7 Deenergize the loop for at least 5 sec.  
7.3.8 Energize the loop. The standby mode shall be set in 10 s.  
7.3.9  When  the  infrared  beam  is  totally  obscured  between  the  receiver  and 
transmitter  for  at  least  5  sec,  the  detector  will  remain  in  the  standby  mode.  If  the 
obscuration  of  infrared  beam  remains  for  more  than  5  sec  but  less  than  15  sec,  the 
detector in 5 sec will go to the fault mode for (51) sec and issue the FAULT message to 
the  loop  and  again  will  go  to  the  standby  mode.  If  the  obscuration  of  infrared  beam 
remains for more than 15 sec,  the detector issues the FIRE message in the loop.  
  
Detector should be checked for proper operation at least once every 6 months in 
accordance with p.7.3. When the CALIBRATION button switch on Rx is switched over, the 
detector should be in standby mode. If the mode of indicators changes calibration should 
be made according to p.7.2. 
9.1 The detector is warranted by the manufacturer for 18 months upon the date of 
the detector's commissioning  but not longer than for 30 months from the date of approval 
by the quality control department of the manufacturer. 
9.2 The  manufacturer  repairs  or  replaces  detectors  within  the  guarantee  term 
provided that the rules of installation, timely maintenance, transportation and storage of 
detectors have been kept.  
9.3 In  the  case  that  faults  according  to  the  reclamation  have  been  removed  the 
guarantee term is prolonged for the while detectors were not in use because of faults. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 