• Do not remove the device front panel while using this device.
• Beofre inserting the device into the breaker compartment,
CORRECTLY IDENTIFY LINE AND BUS TERMINALS FOR THE
BREAKER COMPARTMENT and visually make certain that the
correct Electrical Ground and Test Device is being used. The device
should connect to the Line Terminals.
• Check the dielectric integrity at 27kV AC across terminals to ground
with grounding switch open.
Typical procedures for use of this device are as follows:
(A) For Grounding
1. With the device out of the breaker compartment, correctly identify
Line and Bus Terminals for the Breaker Compartment and visually
make certain that the connections will be made to the Line Terminals.
2. Life the device and load it on to the extension rails of the breaker
compartment with extreme care.
3. Push the device to the "Test" position as indicated by the crisp clicking
sound of the levering latch engaging the levering nut.
4. Using the breaker levering crank, lever the device to the "Connected"
position as indicated by the red flag appearing in front of and under the
levering crank.
5. Unlock and open the test ports and test for "dead" circuit using
correctly rated neon test stick or equivalent.