AKO 520622 Руководство - Страница 8
Просмотреть онлайн или скачать pdf Руководство для Система безопасности AKO 520622. AKO 520622 12 страниц.
Installation
3.-
The alarm should be installed in a place protected from vibrations, water and corrosive gases, where the ambient
temperature does not exceed the value indicated in the technical data. The station should be installed in a place
where the regular presence of people who can alert to the presence of alarms is guaranteed.
In order for the alarms to have IP65 protection, must use the appropriate cable glands.
Station assembly
- Remove the cover T of the equipment (Fig. 1).
- Open the equipment and remove the front of the housing (Fig. 2).
- Drill the holes needed for the cable entry glands using the pre-stamped centres on the sides of the housing for
guidance.
- Drill 3 holes on the wall following the fixing holes 1, 2, 3. (Fig. 3).
- Fasten the glands into the equipment.
- Insert the 3 screws and wall plugs through the housing into the holes in the wall and tighten.
- Insert the cables through the glands.
- Fit the front of the housing (Fig.2).
- Insert and tighten screws D, F (Fig. 1).
- Connect the cables as shown in the wiring diagram, close the cover T, insert and tighten screws A, C (Fig. 1).
BASIC
BASIC
FIG. 1
FIG. 2
8
5206H701 Ed.03
222,1 mm
140 mm
FIG. 3