AKO Electronica AKO-15223 Руководство

Просмотреть онлайн или скачать pdf Руководство для Термостат AKO Electronica AKO-15223. AKO Electronica AKO-15223 2 страницы. Configurable electronic thermostats with 2 relays and up to 2 probes

1472H206
HOJA TÉCNICA
Configurable electronic thermostats
GB
with 2 relays and up to 2 probes

Panel mounting

Rail DIN
tion and adjustment that the device's use requires. The functions of the front part keys as well
as the display of temperatures can be modified, while the configuration with a password can
be blocked.

Examples of some of the many applications

Heat:
Thermostat with two probes to display and
control.
Thermostat with control relay and alarm relay.
Action thermostat by a temperature difference
between the two probes.
As two simple thermostats.
As two cyclic timing devices without enabling
the probes.

Index:

1- Versions and references
2- Technical data
3- Installation

4- Front panel functions

5- Configuration and adjustment
1 - VERSIONS AND REFERENCES
MODEL
AKO-14722
FASTENING UNIT
Panel mounting
POWER SUPPLY, 50/60Hz
12V ±20%
2 - TECHNICAL DATA
Temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (-58ºF a 211ºF) -50ºC a 99ºC
S1 input for NTC probe: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149XX
S2 input for NTC probe: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149XX
Controller accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1ºC
Probe tolerance at 25ºC: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±0,4ºC
Relay R1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16(4)A*, 250V, cosϕ=1, SPST
Relay R2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8A*, 250V, cosϕ=1, SPDT
Maximum input power:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5VA
Working ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5ºC a 40ºC
Storage ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30ºC a 70ºC
Installation category: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II según norma CEI 664
3 digits and an optional decimal point when programmed
Double insulation between the power supply, the secondary circuit and the relay output.
* The current specified for each relay is its individual maximum. When more than one relay is
connected, the total current cannot surpass 17,5A (EN61010) or 13A (EN60730).
3 - INSTALLATION
The controller must be installed in a place protected from vibrations, water and corrosive gases,
and where the ambient temperature does not surpass the values specified in the technical data.
In order for the panel mounting units to be suitable having IP65 protection, the gasket should
be installed properly between the apparatus and the perimeter of the panel cut-out where it is
to be fitted.
In order to give a correct reading, the probe has to be installed in a place without heat influen-
ces other than the temperature that is to be measured or controlled.
3.1 Fastening units for panel mounting:
PANEL CUT-OUT
70,5
3.2 Fastening units for DIN rail mounting:
3.3 Connection:
See diagram in the unit rating plate.
The probe and its lead shoud NEVER be installed in ducting along with power, control or power
supply wiring.
The power supply circuit should be connected with a minimum 2A, 230V, switch located close
to the unit. The cables should be of the type H05VV-F 2x0,5mm
Section of connecting wires for relays contacts must be between 1mm
Edición 01
The two probe inputs can be inte-
rrelated with the two relay outputs
for the thermometer, thermostat
and the timing functions in cold and
heat applications.
CONFIGURATION
some parameters are ADJUSTA-
BLE or not by the USER so that he
or she has the exclusive informa-
Cold:
Double controller with defrost by compressor
stop.
Simple controller with defrost by compressor
stop and alarm relay.
Simple controller with defrost by air.
Simple controller with defrost by electric heat.
Thermostat with two phases or with a neutral
zone.
10 - Warnings
AKO-14723
Panel mounting
~
230V
±10%
max.
To fix the unit, place the faste-
18 mm
ners 1 over the sliders 2 as
3
shown in the figure. Move the
2
1
fasteners in the direction of the
arrow. By pressing tab 3 the fas-
teners may be moved in the
opposite direction of the arrow.
61,5
58
2
or H05V-K 1x0,5mm
2
and 2,5mm
4 - FRONT PANEL FUNCTIONS
4.1 Panel mounting models:
LED R1
ºC
1
2
3
4
LED R2
allows
that
4.3 Common functions:
UP key (factory default)
By pressing this key, the temperature in probe 2 is displayed.
By pressing it during 5 seconds, the R2 SET POINT is displayed.
In programming, it increases the value being displayed.
UP key (configurable)
By default, the configuration of this key is factory-set for the preceding actions. However,
it can be configured according to the options of parameters 42, 43.
DOWN key (factory default)
By pressing this key during 5 seconds, the R1 SET POINT is displayed.
In programming, it decreases the value being displayed.
DOWN key (configurable)
By default, the configuration of this key is factory-set for the preceding functions.
However, it can be configured according to the options of parameters 44, 45.
+
UP + DOWN keys (in panel mounting models)
Pressing these keys during 10 seconds accesses to the configuration of the contro-
ller parameters.
+
UP + DOWN keys (in panel mounting models)
Pressing these keys once accesses to the adjustment of the user's parameters.
By default, the configuration of these keys is factory-set for the preceding function.
However, they can be configured according to the options of parameter 46.
LED ºC Permanent: Temperature display in ºC.
Flashing:
LED ºF
Permanent: Temperature display in ºF.
LED R1 Permanent: Relay R1 activated.
LED R2 Permanent: Relay R2 activated
AKO-15223
DIN Rail
~
5 - CONFIGURATION AND ADJUSTMENT
230V
±10%
CONFIGURATION: It should only be programmed or modified by personnel who are fully con-
versant with the operation and possibilities of the equipment.
Level 1
Parameters
- Press the CONFIGURE OR ADJUST keys for 10 seconds. The LED "ºC" will be flashing to
indicate programming phase and the first parameter "01" will appear on the display.
- Pressing the ( key accesses the next parameter and the ( key will produce a return to
the previous one.
- Pressing DISPLAY VALUE key in the last display EP the controller will return to the current
temperature display status and the LED "ºC" will stop flashing.
Level 2
Values
- In order to display the current value of any parameter, select the desired parameter and
press the DISPLAY VALUE keys. Once it is displayed, it can be modified by pressing the
( or ( keys
- Pressing the ACCEPT THE NEW keys sets the new value. When this operation is performed,
the programming returns to Level 1 (parameters).
TEMPERATURE
ºC
ºF
SET
ADJUSTMENT: Pressing once the CONFIGURE OR ADJUST keys accesses the user's para-
meters adjustment. The proceeding is the same as for the configuration and access is only
possible to the parameters defined as adjustable by the user in the configuration. In order to
access the parameters the parameter 39 parameter should be configured.
REMARK: If no key is pressed for 25 seconds in any of the previous steps, the controller will
automatically return to the current temperature display status without modifying any of the
2
.
parameters values.
2
( 01 de 02 )
www.ako.com
4.2 DIN Rail models:
LED ºC
LED ºC
LED ºF
UP
ºF
key
PRG
SET
DOWN
key
Parameters programming phase.
CURRENT
LEVEL 1
PARAMETERS
10 Sec.
SIMULTANEOUSLY
SIMULTANEOUSLY
10 Sec.
CURRENT VALUE
EXIT
PROGRAMMING
LED ºF
UP
ºC
key
ºF
SET
key
DOWN
key
1
2
3
4
LED
LED
R1
R2
SET key (in DIN rail models)
SET key (in DIN rail models)
LEVEL 2
VALUES
SIMULTANEOUSLY
NEW VALUE