Installation and Operating Manual
Pulse relay SIR 8 AN
General information
Pulse relay SIR 8 AN is a system component for the SI building management system 
for retrospective installation in distribution boxes or consumer devices. The SIR 8 AN 
can be controlled as a normal monostable relay or a pulse relay via various inputs. 
The relay is fitted with an integrated 24 V DC extra-low voltage adaptor for control-
ling the inputs. The isolating distance between the control circuit and the operating 
voltage  on  one  side,  and  between  the  control  circuit  and  load  circuit  on  the  other, 
meet the provisions for electrical separation given in DIN VDE 0100 Part 410. If the 
provisions for electrical separation between the extra-low voltage and mains voltage 
are observed even during wiring, the control switch for the SIR 8 AN or other com-
mand devices as well as the control lines must be designed solely for operation with 
extra-low voltage. Simple unshielded control lines (e.g. IYY or IYSTY) can be used in 
this case. If the relay is combined with operating devices or lines in the control circuit, 
which do not meet the requirements for extra-low voltage, the protective measures 
for a functional extra-low voltage of 24 V DC must be applied.
Input/output functions
When pulse functions are in use, only switching on the control voltage will have an 
affect. Continuous voltage on one or more pulse inputs will not change the switching 
status and does not disrupt the function when controlling the other inputs. Switching 
on a continuous control voltage via monostable input A1 takes precedence over all 
other control commands on the pulse inputs.
Input/output
Function
Control input for monostable functions, output for connecting 
A1
an external switch position indicator
A2
Control input on/off
A3
Control input off
A4
Control input on
18
Load output
0 V / 24 V
Output voltage, integrated DC adaptor
Mounting
Installation  may  only  be  carried  out  by  an  authorised,  trained  technician.  The 
SIR 8 AN is especially designed for installation in switch or junction boxes.
Requirements for command devices
Any device with outputs that function as on/off switches on 24 V DC are suitable for 
use as command devices. The following criteria must be met:  
1.  The bounce time when the contact closes must not exceed 10 ms.
2.  The maximum contact resistance Rmax must not exceed 1 Ω.
All  conventional  switches  with  mechanical  contacts  meet  these  criteria.  However, 
special attention concerning these requirements must be given to command devices 
with semiconductor outputs.
Important information: When controlling more than one pulse relay centrally via a
keypad, only the +24 V DC outputs of the individual adaptors are through connected.
The 0 V potentials must not be connected, as parallel connection of the adaptors is not
permitted.
Guarantee
All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory guarantee period from the day of purchase by the end user. The guaran-
tee is not applicable to damage incurred during transport or caused by short-circuit, 
overloading  or  improper  use.  In  the  event  of  defects  in  workmanship  or  material, 
which are discovered within the guarantee period, the company will provide a repair 
or  replacement  free  of  charge.  The  guarantee  will  be  rendered  null  and  void  if  the 
device is opened without authorization.
3931108  |  11/2013  |  Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden
Technical Data
SIR 8 AN
Operating voltage
Internal consump-
tion
Control voltage
Control line length
Permitted switch 
bounce time
Required control 
pulse duration
monostable function takes precedence, output for external 
A1
A2
Inputs
A3
A4
Load output
relay contacts, internally connected to mains voltage
Rated voltage
Rated current
Endurance  
at rated load
Protection class
Housing
Terminals
Clamping area
Ambient tempera-
ture
Wiring
SIR 8 AN
A 2
A 4
A 3
A 1
0 V
24 V
N
L
18
230 V AC
max. 400 mW
integrated adaptor, 24 V DC 
max. 1000 m with a diameter of 0.6 mm
max. 10 ms
min. 20 ms
switch position indicator (max. 6 mA)
alternates on/off
off
on
230 V AC
8 A
> 100,000 cycles
IP 40
ABS
spring loaded terminals 
0.4 mm – 0.8 mm
-10 °C to +45 °C
L
N
Steuereingang ein / aus
(control input on / off)
ein
(on)
aus
(off)
monostabil ein
(one-shot on)
externe Anzeige
(external display)
24 V DC
0 V DC