Sensors
The sensors must be connected to the exact ports on the screw terminals as illustrated below. Max current per port is
Minimum cable size depends on the distance to the sensor, please refer to the table below:
2
Distance
mm
<50 m
Min. 0.5 mm
50-100 m
Min. 0.75 mm
100-150 m
Min. 1.0 mm
The iDOL 63 has 8 input ports for connection of DOL sensors.
Ask your dealer for a list of supported DOL sensors.
Each port works independently and must via the Omni Cloud be configured in accordance to the connected sensors. Each port has a plug for 24 V
power supply (1), a plug for the DOL sensor output signal (2) and a ground plug (3). To connect a DOL sensor, the process is as follows:
1)
Make sure there is no power on the iDOL 63
2)
Select which port to use. DOL 19 may only be plugged into port 1 and 2, whereas the other supported DOL sensors may be plugged into
any of the 8 ports. You may only connect one sensor to a port
3)
Follow the TUG for the selected sensor to connect power, signal and ground correctly
4)
Connect POE (power and internet connection, the RJ45 internet connector)
5)
Update Omni Cloud in accordance to which sensors you have connected to the individual ports. Follow the Omni UI User Guide or
handover the information to the owner/administrator of the Omni Cloud account
dol-sensors a/s
AWG
2
Min. 20 AWG
2
Min. 18 AWG
2
Min. 17 AWG
Agro Food Park 15 - 8200 Aarhus N - T: +45 7217 5888 - F: +45 7217 5959
83 mA.
www.dol-sensors.com