6.2 CALIBRATING VALVE POSITION
The valve must be calibrated to ensure the position of the valve is accurate.
Press & hold both the open & close buttons for approximately 15 seconds to access the setup menu with the OEM
Configuration option visible.
Navigate to the Valve Calibration screen - Menu location: Setup Menu → OEM Configuration → Valve Setup → Valve
Calibration.
The screen will display the following warning: "The valve will fully open and close during calibration." After you have
verified that the valve is properly installed to the motor, and there is no danger of damage due to water in the line,
press ■ START to begin the calibration process.
The valve will fully open and close twice to calibrate the valve position sensor. After calibration is complete, press the
■ OK button to return to the Valve Setup screen.

7 OPERATIONAL FEATURES

The Style 9333/9335 Navigator Pro Controller has been designed to be intuitive and easy to use. Once configured,
the operation is simple. Basic operation of the controller is described below.

7.1 Opening and closing the valve

To open the valve using the Navigator Pro, press the GREEN button. To close the valve, press the RED button. As
soon as either button is released, the valve will stop moving. To continue opening or closing the valve, continue to
hold the appropriate button.
Wiring Harnesses & Components
Description
9333 Valve Controller
9335 Valve Controller
Power Harness
Motor Driver
Motor Extension Harness
Main Harness – 10'
Main Harness – 15'
Main Harness – 20'
Pressure Transducer Adapter Harness
Flow Sensor Adapter Harness
Part Number
93330001
93350001
721359
124647
721769
721618
721619
721620
721770
721771
Page | 5