GCU - MP3 Manual
detect outage signal.
※
Warning
flickers.
8. Connection Sockets and Capacity
Socket Name
BP+, BP-
Control Power Input
88x
Start Output
5x
Stop Output
PH+
Preheating Output
CP1, CP2
Commercial power input platform
GP1, GP2
Generator power input platform
Input socket when using voltage for engine
GS1, GS2
speed detection
MP1, GS2
Engine operation signal input socket
Automatic start interface(commercial power
CNT
UVR input)
TM+
RPM METER connection socket
52C, TXA
Block circuit breaker interface
52C, CXA
Input of circuit breaker interface
86XA, 86XC
Breakdown display interface
6XA, 6XC
Engine operation display interface
WTS
Input of high temperature switch
OPS
Input of oil pressure switch
EPB
Input of emergency stop switch
GR
Input of ground over current relay
OVR
Over voltage input socket
OCR
Over current input socket
Low voltage input socket (works when
UVR
revolution speed of generator is above 70%
of normal revolution speed)
52GC
Input of circuit breaker input signal
52GT
Input of circuit breaker blockage signal
G+
Gauge power output above IDLE SPEED
5EX-S
Emergency Stop assistant output
51X-S
OCR assistant output
59X-S
OVR assistant output
12X-S
Over Speed assistant output
48X-S
Automatic mode start failure assistant output
63Q-S
Low oil pressure failure assistant output
26W-S
Over temperature failure assistant output
27Y-S
UVR assistant output
9. Manual Start Test
9.1. Manual mode lamp is on when selected manual mode by pressing manual mode button
9.2 When pressed start button battery "+" is out from 88X socket and runs 88 (start assistant magnet)
to start engine.
(1) Power of starter motor is cut when engine revolution speed is above IDLE SPEED or oil pressure
switch is open
(2) RUN lamp is on when engine revolution signal entered to GS1/GS2 socket or MP1/GS2 socket is
greater than IDLE SPEED.
(3) When oil pressure switch is not open for more than 5 seconds in IDLE SPEED, low oil pressure
Upon input of power, control power lamp is on and lamp near wrong wiring
Description
EGCON CO., LTD
Rated Capacity
DC 8~35V , 15A
BP+ voltage output, Max 15A
BP+ voltage output, Max 15A
BP+ voltage output, Max 15A
1P 220Vac
1P 220Vac
1P 220Vac
MPU signal
Automatic mode, work upon connect
DC
connect RPM METER "+" socket
Dry contact , AC300V, 10A (2sec)
Dry contact , AC300V, 10A (2sec)
Dry contact , AC300V, 5A
Dry contact , AC300V, 5A
NORMAL OPEN , connect DC-
NORMAL CLOSE, connect DC-
NORMAL OPEN , connect DC-
NORMAL OPEN , connect DC-
NORMAL OPEN , connect DC-
NORMAL OPEN , connect DC-
NORMAL CLOSE, connect DC-
connect DC-
connect DC-
BP+ voltage output, Max 5A
DC- output , below 500mA
DC- output , below 500mA
DC- output , below 500mA
DC- output , below 500mA
DC- output , below 500mA
DC- output , below 500mA
DC- output , below 500mA
DC- output , below 500mA