Egcon MP3 Руководство пользователя - Страница 7

Просмотреть онлайн или скачать pdf Руководство пользователя для Блок управления Egcon MP3. Egcon MP3 9 страниц. Acu (ats control unit)

ACU-MP3 Manual
Before wiring, please block all the power supplies into ATS.
7.1. Please connect ATS to ACU-MP3 according to [Circuit Diagram 1].(If connecting COM
power with 1P 220Vac, please connect according to [Circuit Diagram 2].
7.2. Please supply power to ATS after checking whether COM power and GEN power is
correctly wired.

8. MANU Operation Test

8.1. When power is applied, ACU operates at the latest selected mode.
8.2. When commercial power and generator power is applied, lamps of both powers turn on.
8.3. If commercial power lamp blinks, it is phase-absent or low voltage so that it needs to be
checked.
8.4. If commercial power is normal and ATS is on the commercial power's side, UVR
contacts(ST1, ST2) of commercial power get OPEN.
8.5. Using generator power selection switch, transfer ATS to generator power's side.
8.6. If ATS is transferred to generator power, insertion lamp of generator power turns on.
8.7. Using commercial power selection switch, transfer ATS to commercial power's side.
8.8. If ATS is transferred to commercial power, insertion lamp or commercial power turns on.

9. AUTO Operation Test

9.1. Using MODE switch, set operation mode for AUTO mode.
9.2. Make commercial power or one of the three phases OFF.
9.3. If power of phase T is OFF, all lamps of ACU gets OFF; if phase R or S is OFF or low
voltage occurs, indication lamp blinks.
[Circuit Diagram 2]
EGCON CO., LTD