Output Voltage Low
Output Voltage High
Output Voltage High-
No Adjustment
Rating Output
Voltage at no load and
Voltage Down at load
condition
Remote voltage Adjust
Operates backwards
Generator Output
Voltage Hunting
Poor Regulation
Incorrect connections.
Voltage adjust turned down.
Remote voltage adjust is turned down.
Defective regulator.
Voltage adjust turned too high.
Remote voltage adjust is turned too
high
Defective regulator.
Generator defective
Voltage adjust wire backwards.
Defective regulator
Defective regulator.
Check wiring diagram for proper
connections.
Incorrect sensing voltage connection can
cause output voltage low-no adjustment.
Rotate voltage adjust CW until desired
voltage is reached.
Rotate remote voltage adjust CW until
desired voltage is reached.
Replace regulator.
Rotate voltage adjust CCW until desired
voltage is reached.
Rotate remote voltage adjust CCW until
desired voltage is reached.
Replace regulator.
Check the generator exciter and rotating
diode
Reverse the wiring of the connection on
the remote voltage adjust.
Rotate the stability adjust in a CW
direction until hunting stops
Replace regulator.