NOTES:
NETWORK. Master-slave (Network)
communication is by shielded twisted
pair cable, RS485 compatible such
as Belden 9841. Maximum overall
system length of 1650ft Connect
screen to C0. NOTE: Diagram shows
a master and ONE slave
configuration**. Wire further slaves in
parallel.
REMOTE SWITCH INPUTS should
be connected by 18 Awg cable. Max
length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate from
mains wiring to minimize noise pick
up. Set within Engineers functions
for all remote sensors.
MODULATION
0-10V outputs should be connected
by 18 awg cable. Max length is 325ft.
GND
U
V
W
Exhaust
Fan
(n.c.)
SmartCom Mulitizone
Burners
(Slave 1)
Zone B
41
40
7
8
R
C
40VA
L2
Trans
L1
G
S-0700
Relay
Burners
SmartCom Mulitizone
Zone A
(Master)
41
40
7
8
S-0700
Inverter Panel
9
25
14
5
6
1/L 2/N
10
LIVE
S/R0S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
NEUT
Black Bulb
GND
120V 60Hz 1 Ph
L2
15 amp Supply
L1 (HOT)
9
25
14
5
6
1/L 2/N
10
LIVE
S/R0S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
NEUT
R
C
Black Bulb
Black Bulb
40VA
Sensor
Sensor
L2
Trans
120V 60Hz 1 Ph
L1
20 amp Supply
G
GND
Relay
L2
L1 (HOT)
230V 60Hz 3 Ph
Supply
L1
L2
L3
To other slave
controllers
Sensor
eg E.M.S.
Outside
Sensor
(where applicable)
eg
To other slave
E.M.S.
controllers
Drawing No. :
900290VDF R6 3P USA