amc VIBRO AVM 1002D Kullanıcı Kılavuzu - Sayfa 11

Ölçüm Cihazları amc VIBRO AVM 1002D için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. amc VIBRO AVM 1002D 14 sayfaları. Vibration monitoring system with relay outputs

amc VIBRO AVM 1002D Kullanıcı Kılavuzu
7.9

Selecting the measured vibration signal estimate 'AU'

The AVM 1002D module enables measuring RMS or 0-PEAK values of vibration acceleration or velocity.
ATTENTION! The configuration must be confirmed using SW1 and SW2 configuration switches
described in the following chapter.
To select desired estimate one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the 'AU' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select one of the following option:
'PU' – 0-PEAK value of the velocity signal,
»
'rU' – RMS value of the velocity signal,
»
'PA' – 0-PEAK value of the acceleration signal,
»
'rA' – RMS value of the acceleration signal.
»
5. To confirm the change, press the SET button.

8. Measurement parameter configuration

Measurement parameter configuration is set by proper set-up of configuration switches SW1 and
SW2. Description of switches SW1 and SW2 is presented in the following table and Figure 8-1:
SW 1
S1 – ON, HPF =10Hz (OFF = 3Hz)
S2 – range 100
S3 – range 10
S4 – range 25
S5 – LPF = 1kHz
S6 – LPF = 10kHz
S7 – acceleration
S8 – velocity
11
Functions of configuration switches
S1 – ON, range 10 (OFF, range 100)
S2 – ON, range 25 (OFF, range 100)
S3 – ON - acceleration (OFF - velocity)
S4 – ON - RMS (OFF - PEAK)
S5 – ON, internal power supply +24V for 4..20mA
S6 – ON, external power supply for 4..20mA
SW2
AV MONITOR 1002D