INSTALLATION
Step 1 – Drilling hole:
It is recommended that the saddle/sensor not be located on the very top or very bottom of
the pipe. Ideal performance can be achieved with the saddle mounted at 2 to 4 o'clock or 8
to 10 o'clock. Hole should also be drilled perpendicular to the pipe centerline and tangent to
the curvature.
Step 2 – Mounting the saddle:
The saddle will need to be preassembled to insure the fit is proper. Assemble the hardware
as shown in Figure 1. Tighten only the bottom nuts that hold the threaded studs to the
saddle.
Figure 1
Place gasket over hole in pipe, place pre-assembled saddle from above over gasket. Be sure
saddle engages hole properly and saddle contour matches pipe's outside diameter. Attach 2
each band clamps as shown in Figure 2 and tighten with 7/16 inch wrench. Recommended
Torque is 75 IN-LB.
NOTE: Clamps can loosen when mounted to plastic pipe, due to thermal contraction.
Figure 2
8