Installation instructions & recommendations for electricians
1. The receiver and Handset portions are for indoor use only or must be protected against moisture.
2. AS/NZS60335-1:2011 Clause 7.12.2 states the following: "If a stationary appliance is not fitted with a supply cord and a plug, or
with other means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection
under over voltage category III conditions, the instructions shall state that means for disconnection must be incorporated in the
fixed wiring in accordance with the wiring rules"
3. Therefore, to comply with the above this system must be connected via a switch that is accessible to the user or a suitably labelled
all-pole RCD that is dedicated to ceiling fans only. Emergency disconnection under fault conditions is not covered by warranty. This
requirement applies to all ceiling fans and remote controls of any make. Owners must be aware of the warranty limitations if unit
is installed without an isolating switch.
4. DO NOT INSTALL IN THE CEILING OR WALL CAVITY. This may exceed its maximum operating temperature, reduce its life
or make it work erratically and WILL void warranty.
5. An internal, non-replaceable high rupture capacity fuse is fitted in the receiver. If an in-situ receiver is open circuit then check for
a fault in the attached fan or light before replacing and possibly damaging another receiver. The maximum total load is 300VA.

Wiring connection:

Wire the remote control receiver to the fan and light using the wiring tails as follows:
a. The fan and light must be earthed. The earth wire is run directly to the earth terminal of the fan/light.
b. Active and neutral are connected to the brown (A) and blue (N) input wires of the receiver.
c. The fan active wire is connected to the brown output wire, the neutral to the blue output wire. The light active is connected to the red
(or white) output wire and the light neutral is connected to the blue output wire (same as the fan). Do not allow any active/neutral
to bypass the receiver or damage may result.
d. Place the receiver into the under ceiling canopy within the space provided in the suspension bracket. Do not place in ceiling cavity.
e. Test system. Show user how the isolation switch or RCD works. Label the switch or RCD accordingly (eg. "Ceiling Fans").
One isolation switch per fan must be used. Typically this is a light switch in the room containing the fan/
light. If an isolation switch is not fitted the unit cannot be paired/programmed and may result in unnecessary
service calls being charged to the owner. Re-programming and pairing is not covered under warranty.
POWER OUTLETS OR FIXED WIRING MUST BE INSTALLED BY A LICENSED ELECTRICIAN
To protect your customer's WARRANTY please READ PAGE 2 of this booklet prior to the installation of this product.