DAB ACTIVE JC132 Kurulum ve Bakım Talimatı - Sayfa 7

Su Pompası DAB ACTIVE JC132 için çevrimiçi göz atın veya pdf Kurulum ve Bakım Talimatı indirin. DAB ACTIVE JC132 20 sayfaları.

DAB ACTIVE JC132 Kurulum ve Bakım Talimatı

4.2 Control panel functions

There is the possibility of remote signalling of the alarm signal; in fact, on the electronic card, Active
has two male faston outlets ( 4.7 mm ) to allow the connection.
(see fig. 14 on page 27)
Contact characteristics: 24V - 5A – normally open (N.O.)

4.3 Regulating the Start pressure.

To regulate the Start pressure, unscrew the protective cap and turn the green trimmer knob. The pressure may
be set at a minimum of 1.5 bar or a maximum of 2.5 bar. (Fig.2)
START PRESSURE REGULATION
FROM 1.5 TO 2.5 bar
ENGLISH
GREEN WARNING LIGHT ON
− System live or correct operation.
GREEN WARNING LIGHT ON
RED WARNING LIGHT BLINKING
− No water: the pump will perform a series of
− Overheating of the motor.
− Blockage of the pump / motor.
GREEN WARNING LIGHT ON
RED WARNING LIGHT ON
− Protection against excess temperature of hydraulic
Fig. 2
21
automatic restarts.
parts .