1. INTENDED USE OF THE PRODUCT
GC2 group control unit is intended for simultaneous or individual control of several electric
operators (up to 2) from the central switch. You can combine several control units for 4, 8
or more electric operators with one or several central switches. The device has a function
of protection from overpower and simultaneous activation of two move directions (buttons
"Up" and "Down"). You can connect several switches to the control unit.
2. SPECIFICATIONS
Supply voltage
Maximal allowable switching current
Switching voltage
Number of operators controlled
Dimensions
Environment temperature
Housing protection rating as per GOST 14254
Electric protection class as per GOST 27570
3. INSTALLATION
1. Remove protective packaging of the control unit. Remove
the cover of the control unit housing using a screwdriver.
2. Unscrew two fixing bolts of the control unit panel and take
it out of the housing.
3. Connect wiring according to the diagram (Fig. 2).
4. Fix the control unit panel in the housing and place the cover
back.
When installing, protect the device from dust and moisture.
When connecting equipment wires, if possible, use the mount-
ing holes positioned on the side of the terminal block (not on
the top). Before connecting, pierce the rubber plugs using an
awl or a thin screwdriver (Fig. 1) so that the diaphragm fits
tightly the inserted wires.
4. WIRING
Contact function (Fig. 2 and 3)
1. Supply mains neutral ~220 V
2. Supply mains phase ~220 V
3. Direction "A" of operator
4. Common wire of switch
5. Direction "B" of switch
7, 10. Neutral of operator (blue wire)
8, 11. Direction "A" of operator (black wire)
6, 9. Direction "B" of operator (brown wire)
Switch
Installation Recommendations
1. To connect supply mains 220 V 50 Hz, use the wire with double insulation and 1.5–
2.5 mm
cross-section core.
2
2. To connect switches, you can use a wire with 0.75 mm
an electric operator, use a wire with 0.75–1.5 mm
installation, you should use cable pipes with protection rating IP65.
NOTE: If the total power of all electric operators used exceeds 1.5 kW, you should divide
them into groups, power of each is from 1 to 1.5 kW, and connect supply voltage to each
group by an individual cable from the electrical control unit. These groups can be also
distributed between various phases of 3-phase electricity supply network.
GC2 GROUP CONTROL UNIT
R1
com
220 V
L1 N
E
L1
220 V, 50 Hz
N
Fig. 2. GC2 group control connection diagram
INSTALLATION AND OPERATION GUIDE
RollHan
GC2
M
Local switch
Local switch
2
220 V, 50 Hz
≤ 3 А
220±10 V
2
98 × 98 × 56 mm
from –40 to +60°С
IP65
II (no protective grounding
is required)
Fig. 1. Hole making
R2
com
M
cross section core. To connect
2
cross-section core. For outdoor