Astria MONTEBELLO ST Ürün Boyutları

Kapalı Şömine Astria MONTEBELLO ST için çevrimiçi göz atın veya pdf Ürün Boyutları indirin. Astria MONTEBELLO ST 2 sayfaları. See-through direct-vent fireplace

A
B 
in
52-1/8
47-3/8
(mm)
(1324)
(1203)
Framing Should be constructions of 2 x 4 or larger lumber.
(330)
16
(406)
6-1/2
(165)
Inches
(millimeters)
B
A
E
 Dimension B is from fireplace base to top fram-
ing member.
 Dimension C is from fireplace base to centerline
of horizontal vent pipe. Minimum vent framing:
Vent Size
Co-axial DV Collar
8" Inner / 11" Outer
on Fireplace -
27-1/2"
(699mm)
26-1/4"
(667mm)
3-1/2"
(89mm)
46-5/8"
7"
(1184mm)
(178mm)
Gas Inlet
Control Switch
J-Box
Wires Knock-
19-5/8"
Out
(499mm)
Left Side View
Unit Dimensions
(Shown with Outdoor Kit Installed)
P/N 900355-07, REV. A, 11/2017
MONTEBELLO™ ST
C 
D
E 
75-1/2
26-3/8
6
(1918)
(668)
(152)
13
16
(406)
Inches
(millimeters)
C
1-1/2
(38)
2 ft vertical vent and one 90° elbow. For other
OUTDOOR SIDE
venting configurations, see Installation and
Operation Manual.
 1/2" board for platform (shown in gray).
 Dimension E is a 6" clearance from fireplace base
to outdoor surface (e.g., deck, patio, lanai) that is
required as a moisture barrier (not a combustible
clearance) on outdoor side only.
25-3/8"
(645mm)
13-1/8"
(333mm)
5-1/2"
(140mm)
12-3/8"
(314mm)
29-5/8"
(753mm)
(opposite of valve access side)
SEE-THROUGH
DIRECT-VENT FIREPLACE
13
(330)
6-1/2
(165)
C
NOTE: For indoor/outdoor in-
stallations, the control side of
B
the fireplace must be installed
on the indoor side.
D
A
INDOOR SIDE
8" / 11"
Vent / Intake
7-3/8"
(187mm)
Top View
34-3/4"
(883mm)
5-1/8"
(130mm)
41-1/2"
(1054mm)
33-3/4"
(857mm)
50-1/2"
(1283mm)
Front View
INTERIOR
Wall Stud
Combustible
Finished Wall
Materials
Min. 1" *
Header
(25 mm)
Combustible
materials are
allowed on face
of appliance
above this point
2 ft Vertical
Vent and
90° Elbow
Top of
Appliance
Top of Door Frame
FIREPLACE
*Insulation is
(side view)
NOT ALLOWED in
clearance zones
around vent
components.
Keep this area free
from combustible
materials.
Min. 4" *
(102 mm)
Min. 1" *
(25 mm)
2 ft Vertical
Vent and
90° Elbow
Top of
Appliance
Spacers
Top of Door Frame
FIREPLACE
(side view)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Min. 4" *
(102 mm)
Spacers
EXTERIOR
Wall Stud
Combustible
Sheathing
Header
Non-combustible
sheathing required
below this point.
Non-combustible
Extend housewrap
(building paper)
to this point.
Note: Non-combustible
sheathing and
housewrap (building
paper) should extend
to U-channels on
sides and bottom.
*Insulation is
NOT ALLOWED in
clearance zones
around vent
components.
Keep this area free
from combustible
materials.
Page 1 of 2