Astria Fireplaces F1592 Hızlı Başlangıç Kılavuzu - Sayfa 2
Kapalı Şömine Astria Fireplaces F1592 için çevrimiçi göz atın veya pdf Hızlı Başlangıç Kılavuzu indirin. Astria Fireplaces F1592 2 sayfaları. Direct-vent fireplaces
Product Reference Information
Cat. No.
F1591
LIBRA 40CLDMN
F1592
LIBRA 40CLDMP
F1593
LIBRA 40CLDEN
Combustible Shelf Height - Inches (millimeters)
Model
Top Vent - with One 90º Elbow
Secure Vent
LIBRA 40CL
53-7/8 (1368)
f i r e - p a r t s . c o m
Minimum Clearances
Inches (millimeters)
1/2 (13)
Back & Sides
0 (0) from Spacers or
Dimples
Top Spacers
Floor
From Bottom of
64 (1626)
Unit To Ceiling
Vent
3 (77) Top* / 1 (26)
Sides & Bottom
Service Clearances - Feet (meters)
Front, Back &
3 feet (0.9 meters)
Sides
*NOTE: 3" (77 mm) above any horizontal/
inclined vent component.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Printed in U.S.A. © 2016 Innovative Hearth Products
P/N 900661-03 REV. NC 05/2016
LIBRA 40CL
Model
Shipping
Shipping
Weight
Volume
299 lbs.
42.0 cu.ft.
299 lbs.
42.0 cu.ft.
299 lbs.
42.0 cu.ft.
Rear Vent - Straight Out the Back
®
Secure Flex
®
Secure Vent
Secure Flex
55-5/8 (1413)
41-1/8 (1045)
41-1/8 (1045)
A Combustible Wall
may extend to any
length on one side only.
0 (0)
If installed as shown,
0 (0)
opposite side is limited
to 6"
(153
mm).
Vertical Termination
Cap SV4.5CGV-1
(rated for high winds
and freezing conditions)
* Ceiling Firestop/
Spacer (SV4.5VF)
Ceiling Framing
Typical
Installation
Uses 4.5" / 7.5" Secure Vent
Secure Flex
®
Direct-Vent Components
PFS
C
Report No. 14-171
Do not insulate the
space between the
appliance and the
area above it.
Shelf Height
(
see table)
Shelf Above Fireplace
With Rear Venting
Top View of
Fireplace
6" (153 mm)
Combustible Walls
Square Horizontal Termination (SV4.5HT-2)
7"
(178)
12-1/8"
(308 mm)
5-1/8"
(130 mm)
Adaptor SV4.5RCH
10-1/2"
(267 mm)
10-1/2"
6 to 48" Vent Section,
(267 mm)
Telescopic vent section,
Elbow or Appliance
®
Rigid and
Collar
These appliances comply with National Safety
®
Standards and are tested and listed by PFS to
US
ANSI Z21.88 (in Canada, CSA-2.33), and CAN/
CGA-2.17-M91, latest editions, in both USA
and Canada, as vented gas fi replace heaters.
Do not insulate the
space between the
appliance and the
area above it.
Shelf Height
(
see table)
Shelf Above Fireplace
With Top Venting
Mantel Depth
14 (356)
12 (305)
10 (254)
8 (203)
6 (152)
4 (102)
12
6
2
10
8
4
(305)
(254)
(203)
(152)
(102)
(51)
Front or Rear Face
of Appliance
inches (millimeters)
To help minimize water infi ltration it is recom-
mended that the Firestop/Spacer (SV4.5HF) be
installed on the exterior side of the wall.
10-1/2"
(267mm)
NOTE: Center line of
Vent Piping is NOT
the Same as the
See Page 1 for Min.
Center line of the
Distance to Base of Appliance.
Framed Opening.
Specifi cations and clearances are subject to change without notice.
Refer to Installation Manual before installation of these appliances for
updated dimensions and instructions.
Top of
Appliance
3"
(77 mm)
1"
(26 mm)
Page 2 of 2