bolid S2000-SP2 Kullanıcı Kılavuzu - Sayfa 14

Yangın Alarmları bolid S2000-SP2 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. bolid S2000-SP2 18 sayfaları. Addressable two output alarm actuating unit

Parameter
The value of relative humidity on
Humidity
reaching which the output is to be
Increased
turned on (off) for the control program
Threshold
36 (37)
Humidity
The value of relative humidity at which
Decreased
the output is turned off (on) for the
Threshold
control program 36 (37)
The value of gas concentration in ppm
Gas Increased
at which the output is to be turned on
Threshold
(off) for the control program 36 (37)
The value of gas concentration in ppm
Gas Decreased
at which the output is to be turned off
Threshold
(on) for the control program 36 (37)
Enables
Report If Relay
messages about changes in the output
Status Changed
status
Generating events upon a change in
Backup Power
conditions of the backup battery or the
Input Monitoring
second power input of the addressable
device
Warning!
To change configuration parameters, please use UProg utility v.4.1.0.26+

2.2.6 Usage

The unit is operated under an S2000-KDL polling loop controller and S2000M control panel or
Sirius fire alarm control panel.
All operating conditions (control program, time to operate, delay before operating the output) are
defined by configuration parameters of the equipment mentioned above. To get information how to
define an addressable device type and configuration parameters, please refer to operation
documentation for the polling loop controller, S2000M, Sirius, and Orion Pro Suite.
While selecting power supply for the unit, one should ensure that it is able to provide a current
sufficient for powering all actuating appliances connected to the unit.
The power supply should be located at such distance from the unit that the resistance of wires
between the power supply and the unit meets the following condition:
- While being powered by a 12 V power supply: R ≤ 0.25 Ohm;
- While being powered by a 24 V power supply: R ≤ 0.34 Ohm.

2.2.7 Testing Operability

Testing operability is conducted as described in Clause 3.4 of this manual.
Description
or
disables
generating
Range
Default Value
0...100 %
0...100 %
0 ... 100
0 ... 100
Yes
No
On / Off
70
60
40
0
No
On
15