Elevator MAP2 Panel must be provisioned by Cansec each time an additional add-on H1000 is added
48 FLOOR ELEVATOR SYSTEM
This configuration is used when connecting to an elevator of up to 48 floors. This consists of one
MAP2 elevator control panel and two H1000 panels.
MAP2 Elevator Panel
Controls floors 1 to 16
H1000 Panel 1
1. Dipswitch Settings:
OPT1: OFF
OPT2: ON
OPT3: OFF
OPT4: OFF
2. Jumper Setting:
3. Address Setting:
Panel address is set to 1
RS485 communication wires
H1000 Panel 1: Controls floors 17- 32
1. Dipswitch Settings:
OPT1: ON
OPT2: OFF
OPT3: OFF
OPT4: OFF
2. Jumper Setting:
3. Address Setting:
Panel address is set to 1
MAP2 Elevator Control
Installation Guide
H1000 Panel 2: Controls floors 13- 48
H1000 Panel 2
Page 8 of 16