Akytec MU110-6U Kullanıcı Kılavuzu - Sayfa 3

I/O Sistemleri Akytec MU110-6U için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. Akytec MU110-6U 18 sayfaları. Analog output module 6 channel

Description

1
Description
1.1
MU110-6U is an extension module with 6 analog outputs.
The module provides following functions:
module control and parametrization via RS485 network
RS485 Network diagnostics
error and alarm signal generation
Slave in the RS485 network.
The module is to be configured using 'M110 Configurator' software via RS485-USB
interface adapter IC4 (not included). The latest version of the configuration software is
available for download on www.akytec.de.
1.2
The I/O modules of Mx110 series use the common standard RS485 for data exchange.
The serial interface RS485 enables communication via two-wired line in half-duplex
mode. The module supports the Modbus RTU and Modbus ASCII protocols with automat-
ic protocol detection The network consists of a Master device and can contain up to 32
Slave devices. The maximum length is 1200 m. The number of slave devices and net-
work length can be increased using RS485 interface repeater.
Separate devices are connected to a network according to linear (bus) topology. It means
that the line goes from the first device to the second one, from the second one to the third
one, etc. Star connections and spur lines are not allowed.
Line reflections always occur at the open bus ends (the first and the last node). The high-
er the chosen data transmission rate, the stronger they are. A terminating resistor is
needed to minimize reflections. Experience proves that the most efficient practice is to
use terminating resistors of 150 ohm.
The modules can be used as slave devices only. Master device can be PLC, PC with
SCADA software or control panel.
1.3
Enclosure
Terminal blocks
LED "POWER"
LED "RS-485"
LED "FAULT"
Dimensional drawings are given in App. A.
There are three jumpers under the front cover (see Fig. 4.1):
X2 − restore factory settings (see 7)
X3 − service function
X1 − DRAM write-protection (see 4.1.1)
All jumpers are in OFF position by default.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de

Functions

RS485 network

Design

plastic, grey, for DIN-rail or wall mounting
2 plug-in terminal blocks with 24 screw terminals
power supply indicator
flashes at data exchange via RS485 interface
lit when data exchange via RS485 interfaces interrupted
2