Akytec SMI2 Kullanıcı Kılavuzu - Sayfa 6
Monitör Akytec SMI2 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. Akytec SMI2 12 sayfaları. Rs485 display
5.5
In this mode the device works within the factory settings, whereby the parameters configured
by the user are saved and not overwritten. This function can be useful if the device must be
configured and its network parameters are unknown.
To activate this mode, press the RESET button for more than 2 s. The flashing word Fact is
displayed and the device accepts the factory settings (see Appendix D.1).
To disable the mode, the RESET button must be pressed again for more than 2 s or the
command APLY must be sent by the master. The flashing word Fact then fades out and the
device resumes the user parameters. The factory settings are effective as long as Fact is
displayed.
►
If the network parameters are queried in this mode, the values of the saved user
NOTICE
network parameters are returned, not the factory setting.
6 Operation
The operating mode is automatically enabled as soon as the device is supplied with power.
The device supports master and slave modes. The mode can be set in the parameter dEv.r
(see Table D3). The factory setting is 0 (slave).
6.1
In the slave mode the SMI2 receives the data from the master and processes it in
accordance with the operating parameters. The results are shown on the display.
6.2
To enable the master mode, the parameter dEv.r must be set to 1. To do this the "Factory
settings" mode must be temporarily activated (see 5.5).
In the master mode the SMI2 sends requests to the slave device in the set cycle (parameter
SLA.P). The following parameters must be configured:
–
–
–
–
The transmitted values are displayed in the same way in both modes in accordance with the
set operating parameters.
The master mode supports only the protocol Modbus RTU/ASCII
►
NOTICE
The device cannot be programmed in the master mode. To do this the "Factory
settings" mode must be temporarily activated (see 5.5).
6.3
The complete parameter list is provided in the Table D3.
The data type (Int, Word, Float, String, Image) for the data transmission is set in the
parameter dAtA.
For data types Int and Word the transmitted values are displayed with the set decimal point
position (parameter dP).
Table 6.1 Decimal point position
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 ·
Factory settings" mode
Slave mode
Master mode
SLA.A - Address of the slave in the network
SLA.r - Register number for the request
SLA.P - Query cycle with increment of 100 ms, standard value – 10 (= 1 s)
SLA.F - Modbus reading function (0x0003 or 0x0004)
Operating parameters
Parameter dP
0
1
2
3
4
Display
----
----.
---.-
--.--
-.---
Factor
1
1
-1
10
-2
10
-3
10
www.akytec.de
5