Akytec PVT10 Kullanıcı Kılavuzu - Sayfa 16
Verici Akytec PVT10 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. Akytec PVT10 17 sayfaları. Humidity and temperature transmitter
Appendix B Connection to the Computer
Address
RW
hex
dec
Change rate limit for temperature
0x00A4 (4)0164 RW
data, °C × 100 / s
Zero adjustment for humidity
0x00A5 (4)0165 RW
data, %RH × 100
Slope adjustment for humidity
0x00A6 (4)0166 RW
data, % × 1000
Change rate limit for humidity
0x00A7 (4)0167 RW
data, %RH × 100 / s
Integrating filter time constant for
0x00A8 (4)0168 RW
all channels, s
Parameter tied to analog
0x00C9 (4)0201 RW
output 1
Parameter tied to analog
0x00CA (4)0202 RW
output 2
Forced value for analog
0x00CB (4)0203 RW
output 1***
Forced value for analog
0x00CC (4)0204 RW
output 2***
Sensor and analog outputs
0x00FF (4)0255 RW
status
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 ·
Description
0...1000 (0.0%...100.0% of output scale)
0...1000 (0.0%...100.0% of output scale)
bit [1] = 0/1 - analog outputs deactivated /
bit[2]= 0/1 - in case of sensor absent, turn
bit[4]=0/1 - in case of sensor absent, turn
Supported values (dec)
1...32000 (0,01...320.00 °C/s),
0 - no limit
-32000...+32000
(-320.00...+320.00 %RH)
-32000...+32000
(-32.000...+32.000 %)
1...32000 (0.01...320.00 %RH/s),
0 - no limit
1...32000 (seconds),
0 - no filter
0 - none
1 - temperature
2 - humidity
3 – dew point
9 - forced Modbus control,
value set in (4)0203
0 - none
1 - temperature
2 - humidity
3 – dew point
9 - forced Modbus control,
value set in (4)0204
bit [0] = 0/1 – sensor present / absent
activated
signaling off/on analog output1
bit [3] = 0/1 – in case of sensor absent,
turn on signaling with low current/high
current on analog output1;
if bit [2] = 0 – this bit will be ignored
signaling off/on analog output2
Default
0
0
0
0
0
2
1
0
0
010110
22d
www.akytec.de
13