by the components chosen for your system, is more generous, but even in these cases it is neces-
sary to evaluate in advance the characteristics and technical data provided for each component
installed.
4- paths with many curves or with very close curves should always be avoided.
English
5- the minimum radius of the curves must be equal to or greater than 0.5 meters.
6- sections of pipes that include both positive and negative siphons must be avoided.
7- the sections of horizontal pipes must be kept perfectly leveled.
8- vertical pipe sections longer than 3.5 meters must always be avoided and at the bases of these
the minimum radius of the bends must be equal to or greater than 1 meter
9- the sections of piping where fuel passes must be well fi xed at least every 1.5 meters.
10- the pipe sections may be built-in or installed under fl ooring, but only for very short linear traces
and only by inserting them into an additional casing pipe of properly larger diameter.
It is recommended to use only pipes, fi ttings and accessories present in our catalog, as they have
been designed, tested and built specifi cally for these systems.
Before installation and start-up of the system, it is essential to carefully read the instructions sup-
plied with the various components and in case of doubts it is advisable to contact specialized
personnel.
The realization of the systems and the installation of the components must always meet the
safety standards corresponding to the type of rooms in which they are positioned.
6.2 Positioning
The suction case should be fastened to the wall of the tank with easily removable screws, through
the holes already available on the frame, taking care to ensure that the protection is positioned above
the rod-crank mechanism.
It is necessary to leave a free space of adequate size all around the machine, in order to permit any
repair, maintenance or inspection operation.
Remember that to remove the protection crankcase it is necessary to remove the suction case from
its seat. Therefore, in order to avoid the outgo of the fuel from the tank, a shutter that can be closed
from the outside of the tank must be installed.
For this purpose our shutter module can be useful.
9