Baumer CleverLevel PL20H Kullanım Talimatları Kılavuzu - Sayfa 14

Aksesuarlar Baumer CleverLevel PL20H için çevrimiçi göz atın veya pdf Kullanım Talimatları Kılavuzu indirin. Baumer CleverLevel PL20H 44 sayfaları.

Baumer CleverLevel PL20H Kullanım Talimatları Kılavuzu
CleverLevel
Adaptive trigger – hygienic/industrial
14.3 Window trigger
The window trigger is used to cause a sensor switch to react within a specific range, for example, in order
to isolate a specific medium. The switching window can be configured within a range from 0 ... 100 %. The
window trigger is recommended for detecting and separating different layers, for example oil from water or
foam from beer.
Signal
(%)
I
I
II
1
2
0
20
50
1
Good conductive medium
2
Adhesion from good conductive adhesive
medium
3
Oily medium
4
Air
14.4 LED factory settings
LED function*
SW1
SW2
0
0
1
0
0
1
1
1
Error
Error
Short circuit
Short circuit
*1 = active, 0 = inactive
14 / 44
Level measurement
®
PL20H/S
II
3
4
80
100
Sweep Range (%)
LED color
Green
Yellow
Cyan
Blue
Flashing red
Red
Operating Instructions
Configuration example for a vessel that can be
filled with either a good conductive adhesive
medium (e.g. fruit preparation) or with an oily
medium (e.g. chocolate mix).
Switch windows I and II in this example are set to
achieve the following goals:
to detect the fruit preparation (1)
„
„
to exclude adhesion from fruit preparation (2)
„
„
to identify the chocolate mixture (3)
„
„
For more information, refer to the HELP menu in
FlexProgram.
Window trigger – Output setup
SW1 (NO) / SW2 (NO)
Switch window, min.
Switch window, max.
Switch window, hysteresis
Damping
Color examples
YE
YE = SW1 active
„
„
CY = SW2 is active
„
„
BU = Both SW1 and SW2 are active
„
„
GN = Both SW1 and SW2 are inactive
„
„
Factory setting
0 %
75.3 %
2.4 %
0.1 s
CY
BU
www.baumer.com
GN