Service data communication

3.3.3
The service data objects correspond to the standards of the CiA. It is possible to access an object via index
and subindex. The data can be requested or where applicable written into the object.
General information on the SDO
Structure of an SDO telegram:
COB ID
DLC
Command
An SDO-COB ID is composed as follows:
Master -> Sensor
Sensor -> Master
DLC (data length code) describes the length of the telegram. This is composed as follows:
1 byte command + 2 bytes object + 1 byte subindex + no. of data bytes (0 - 4).
The command byte defines whether data is read or set, and how many data bytes are involved.
SDO command
Description
22h
Download request
23h
Download request
2Bh
Download request
2Fh
Download request
60h
Download response
40h
Upload request
42h
Upload response
43h
Upload response
4Bh
Upload response
4Fh
Upload response
80h
Abort message
An abort message indicates an error in the CAN communication. The SDO command byte is 80h. The
object and subindex are those of the requested object. The error code is contained in bytes 5...8.
ID
DLC
580h + Node ID 8
Baumer_GIM500R_CANopen_MA_EN.docx
03.19
Object L
Object H
: 600h + Node ID
: 580h + Node ID
Byte 1
Byte 2
Byte 3
80h
Object L
Object H
Subindex Data 0
Data length
Max. 4 Byte
Transmits parameter to sensor
4 byte
2 byte
1 byte
-
Confirms receipt to master
-
Requests parameter from sensor
Max. 4 byte
Parameter to master with max. 4 byte
4 byte
2 byte
1 byte
-
Sensor signals error code to master
Byte 4
Byte 5
Subindex ErrByte 0 ErrByte 1 ErrByte 2 ErrByte 3
8/29
Data 1
Data 2
Data 3
Byte 6
Byte 7
Byte 8