SSC Configuration

4.3.2
4.3.2.1 Switching Mode
Figure 7 Single Point Mode (O200.G, O200.R)
A single setpoint (SP1) is defined at which the
sensor switches.
Figure 9 Single Point Mode SmartReflect (O200.S)
A single setpoint (SP1) which represents the
position of the reference background.
Parameter name
SSC1 Config.Mode
4.3.2.2 Channel Logic
Allows to change the output logic from Normally Open (NO, Normal) to Normally closed (NC, Inverted).
Single Point Mode
Figure 10 «Normal» or NO setting
The output is high, when the object is
-
within the range defined by the setpoints.
The output is low when the object is not
-
present our outside of the range defined by
the setpoints
Parameter name
SSC1 Config.Logic
en_BA_O200_IO-Link_V1.docx
15.08.2018/
Short Description
Selection of the switching mode
Window Mode
Short Description
Changes the Logic from NO to NC
Figure 8 Window Mode (Only O200.G)
The sensor switches withing a range defined by two
different setpoints (SP1 and SP2)
Rights
rw
Single Point Mode
Figure 11 «Inverted» or NC setting
The output is high when the object is not
-
present our outside of the range defined by
the setpoints
the output is low, when the object is within the
range defined by the setpoints
Rights
rw
12/34
Unit / Allowed values
-
Disabled
-
Single Point
-
Window
(Only O200.G)
Window Mode
Unit / Allowed values
-
Normal (NO)
-
Inverted (NC)