7.3.3.
No position data
Encoder DUO-LED lit green continuous, LED of connected port is green continuous, but PLC does not
recognize any position data.
• The encoder's device name is clear (""), and PLC cannot automatically assign the proper name because
automatic assignment wasn't projected or no Topoplogy Planning was done.
• Make sure the I/O encoder addresses are within the cyclic updated process mapping. Size and position of
process mapping or encoder I/O address may require adjustment.
• No I/O module present in encoder HW configuration.
• No topology planning executed. Other port than projected has been connected (operating modes IRT).
7.3.4.
PLC error LED is lit
Encoder operational, but error LED at PLC is lit
• Operating mode RT: Topology planning executed. Other port than projected has been connected.
• Diagnostic alarm is present