INSTALLATION
Figure 1
Figure 2
SIDE VIEW
MINI
STANDARD
SUPER
A*
100
100
100
B*
510
640
650
C*
1160
1420
1570
Figure 3
PLAN (TOP) VIEW
MINI
STANDARD
SUPER
A*
100
100
100
B*
510
640
650
C*
630
760
760
D*
350
420
430
E*
690
820
820
BUILT-IN INSTALLATIONS
The appliance is deigned to be built into a new or
existing chimneybreast installation to provide efficient
space heating with both radiant and convected heat.
There must be sufficient space in the fireplace recess to
allow air to circulate around to back, top sides and base
of the appliance.
The example fig 1 shows how your Dovre should be
installed in a chimneybreast recess for chimneybreasts
situated internally and externally.
The recess should be formed using an appropriately
designed raft lintel to support the existing structural
brickwork and chimney. The minimum clearances between
the appliance and walls are illustrated in figs 2 & 3.
PROCEDURE
1
Prepare the opening ensuring that adequate support
is
provided
for
the
chimney
and
chimneybreast structure. A raft lintel, to form the top
of the convection chamber, should be constructed.
The lintel should be pre-formed with a clearance
hole of 200mm (for the 1800W series, the clearance
need only be 150mm or 180mm depending on the
diameter of the flue pipe) to allow the connecting
flue pipe to be installed. If the recess is too wide,
reduce the width using 75mm thick building blocks.
2
Line the top, sides and back of the recess (convection
chamber) using Dovre insulated panels. Fix the
panels to the brickwork (aluminium face outwards)
using masonry nails or other suitable fixings.
4
3
If the fireplace is located on an outside wall, install a
standard airbrick or Dovre air control damper (part
number ASI) at floor level. For fireplaces located on
inner walls, it will be necessary to bring an air
supply from under the floor.
AN AIR SUPPLY IS PARTICULARLY IMPORTANT IN
WELL-INSULATED ROOMS.
4
Stand the appliance in the recess and adjust the
levelling bolts on the bottom of the legs to ensure the
appliance is level and plumb.
5
Use a length of 316 grade 1mm thick stainless steel
flue pipe or other pipe which complies with Current
Building Regulations for the installation of solid fuel
burning appliances, connected from the flue spigot on
the appliance to the main chimney. See fig 2 page 4.
ENSURE THAT THE APPLIANCE DOES NOT DIRECTLY
SUPPORT THE WEIGHT OF THE MAIN CHIMNEY OR
CHIMNEY LINERS. THE FLUE LINERS MUST BE
SUPPORTED BY INDEPENDENT BRACKETS.
Construct the hearth making sure that the design and
structure
complies
Regulations.
The finished hearth surface (e.g. hearth tiles) should
be approximately 6mm below the bottom of the
doors. See fig. 2 page 4.
6
Construct the facing wall of the fireplace, using a
lintel to support brickwork / masonry above the
appliance.
NEVER BUILD DIRECTLY ONTO THE APPLIANCE.
50mm thick lightweight building blocks backed
with Dovre insulation panels are ideal for
constructing the facing wall of the convection
chamber. See fig 2 & 3 page 4.
7
Install air grills, total minimum area 600sq.cm at the
highest point of the convection chamber. Install air
grills minimum area 400sq.cm as close to the floor
level as possible. There is no restriction on the
number of grills used.
Where the fireplace backs onto another room, or is
situated in the corner of the room, backing onto two
rooms, grills can be fitted in the adjacent rooms. In
this case, it will also be necessary to fit a return air
grill in the other room or rooms.
NEVER USE GRILLS MADE FROM PLASTIC OR
existing
OTHER COMBUSTIBLE MATERIALS.
MODELS WITH BACK BOILERS
The model 2000MFR is available with an optional glass
lined boiler suitable for direct or indirect cylinders. The
system must incorporate gravity circuit open to
expansion. Pipework must be a minimum diameter of
28mm and must be installed to rise from the appliance.
IT IS RECOMMENDED THAT A QUALIFIED HEATING
ENGINEER IS USED TO INSTALL HOT WATER MODELS.
The chimney is the key to the successful installation of your
Dovre appliance. If the chimney is in poor condition or of
the wrong design or construction, the performance of the
appliance will be adversely effected and problems will be
experienced with combustion and possible smoke emission
to the room.
PLEASE SEEK THE ADVICE OF A CHIMNEY SPECIALIST IF IN
The chimney should be one of the following types:
Brick built with suitable liner for use with
woodburning and solid fuel appliances.
Twin wall stainless steel approved for use with
woodburning and solid fuel appliances.
Prefabricated "concrete" type systems approved for
use with woodburning and solid fuel appliances.
DO NOT USE FLEXIBLE LINERS DESIGNED FOR USE
ONLY WITH GAS STOVES
with
current
Building
MINIMUM 200MM (150MM FOR 1800)
NEVER ALLOW THE APPLIANCE TO CARRY THE
WEIGHT OF THE CHIMNEY.
1800W SERIES / 2700W SERIES
Dry wood (minimum 2 years seasoned), Lignite briquettes
(brown coal), dry peat, Homefire.
Dry wood (minimum 2 years seasoned), Lignite briquettes
(brown coal), dry peat and most manufactured smokeless
fuels.
LIGHTING AND OPERATION
• Place tightly rolled newspaper or firelighters on the grate
of the appliance.
• Place a reasonable quantity of small pieces of dry kindling
wood on top of the newspapers and 3 or 4 pieces of wood
approx. 2.5 to 5cm in diameter on top of the kindling wood.
• Slide the lower and upper air controls to the fully open
position. (1800W is not equipped with upper air controls).
• Open the doors fully and light the front newspaper or
Firelighters with a long taper.
• Immediately after the kindling wood begins to burn,
partly close the doors leaving a distance of 2 - 3cm from the
fully closed position.
• Allow the fire to burn fiercely in order to warm the
chimney as quickly as possible. As soon as the fire is
burning well, add more wood or solid fuel.
• If burning solid fuels, the solid fuel may be placed directly
on the firelighters.
• Ideally your wood should be no more than 10cm diameter.
5
THE CHIMNEY
DOUBT.
CHIMNEY DIAMETER
INSIDE DIAMETER.
FUELS
2000MFR SERIES