Horizon
Chewblet ice machine
5
Remote condensing unit
Important specifier notes:
1. Provide front, back and side clearances
as shown.
2. The maximum refrigerant line run length
is 100 ft (30.5 m). Installations with up to
50 ft (15.2 m) line run require:
1000 Series – 8 lbs (4 kg) of refrigerant
1400 Series – 11 lbs (5 kg) of refrigerant
1650 Series – 11 lbs (5 kg) of refrigerant
(consult installation manual for correct
refrigerant charge if line run exceeds
50 ft (15.2 m).
3. The maximum line rise above
the evaporator is 35 ft (10.7 m).
Condensing unit above evaporator unit –
35 ft (10.7 m) (installations with rise over
20 ft (6.1 m) require additional suction
line s-trap at midpoint rise).
4. The evaporator can only be mounted
a maximum of 15 ft (4.6 m) above the
condensing unit.
Note: The service loop is not included
when calculating length, rise or drop in
the tubing run.
Note: To connect evaporator/ice machine to rack systems, see page 7.
Condensing unit installation specifications
38"
(97 cm)
Follett Corporation
801 Church Lane • Easton, PA 18040, USA
+1 (610) 252-7301 • Fax +1 (610) 250-0696
www.follettice.com
1000 series 1400 series or 1650 series
with remote air-cooled condensing unit
Undercounter/in-cabinet mounting & ventilation
exhaust
48"
(122 cm)
Follett Europe Polska Sp. z o.o.
Mokry Dwór 26C 83-021 Wiślina, Poland
+48 (58) 785-6140 • Fax +48 (58) 785-6159
www.folletteurope.com
air in
48"
(122 cm)
48"
(122 cm)
Form# 3815
5