Set the slide-switch function selector to the 600Ω/ •��/
• 600Ω Resistance range with Audible-Continuity is the default function.
It is an extended low resistance range to complement the Resistance (Ω)
function in AutoCheck
improved drastically (from that of AutoCheck
range architecture. Audible-Continuity is convenient for checking wiring
connections and operation of switches. A continuous beep tone indicates a
complete circuit.
• Press SELECT button momentarily selects Diode test function. The display
shows the approximate voltage drop across the test leads. When forward
biased, normal forward voltage drop for a good silicon diode is between
0.400V to 0.900V. A reading higher than that indicates a leaky diode
(defective). A zero reading indicates a shorted diode (defective), and the
meter gives a continuous beep warning. An OL indicates an 10 open diode
(defective). Reverse the test leads connections (reverse biased) across the
diode. The display shows OL if the diode is good. Any other readings indicate
the diode is resistive or shorted (defective).