(1) Indoor unit address
Rotary switch (IU AD × 1) ......................Factory setting "0"
Rotary switch (IU AD × 10) ....................Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1) ..................Factory setting "0"
Rotary switch (REF AD × 10) ................Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Table A
• If working in an environ-
ment where the wireless
remote controller can be
Address
used, the addresses can
also be set using the
Refrigerant
remote controller.
circuit
• If setting the addresses
0
using the wireless
remote controller, set
1
the indoor unit address
2
and refrigerant circuit
address to "00".
3
(For information on set-
4
ting using the wireless
remote controller.)
5
* Do not set the indoor
10
unit address (IU AD
SW) at 64 to 99.
11
It may result in failure.
99

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Fig. B
Confusion
Indoor unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2, referring to the Table B.
Dip switch "SET 3"
ON
OFF
Table B
A (Factory setting)
DIP switch SET 3 SW1
DIP switch SET 3 SW2

7.3. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00 Standard
Filter indica-
01 Longer
11
tor interval
02 Shorter
00 Enable
01 Disable
Filter indica-
13
Display only on
tor action
02
central remote
controller
(Forbidden)
20
(Forbidden)
23
Rotary switch
Rotary switch
Address
setting
setting
REF AD SW
IU AD SW
Indoor unit
× 10
× 1
× 10
0
0
0
0
0
1
1
0
0
2
2
0
0
3
3
0
0
4
4
0
0
5
5
0
1
0
10
1
1
1
11
1
9
9
63
6
Code change
A
B
C
A
B
C
IU AD
REF AD
RC AD
×10
×1
×10
×1
SET3
SET4
Custom code
B
C
OFF
ON
OFF
OFF
OFF
ON
Default
Details
Adjust the filter cleaning interval noti-
fication. If the notification is too early,
change to setting 01. If the notifica-
tion is too late, change to setting 02.
Enable or disable the filter indicator.
Setting 02 is for use with a central
remote controller.
Function
Function
number
Horizontal
swing airflow
24
direction
(Forbidden)
26
(Forbidden)
27
Cool air
temperature
30
trigger
Heat air
temperature
31
trigger
× 1
0
Auto restart
40
1
2
Cool Air
43
3
Prevention
4
5
0
External
1
46
control
3
Error report
47
target
Fan set-
ting when
cooling
49
thermostat
D
OFF
D
Switching
function for
60
external
inputs
(Forbidden)
61
(Forbidden)
62
D
Auto mode
68
type
ON
ON
Deadband
69
value
(Forbidden)
70
(Forbidden)
72
(Forbidden)
73
(Forbidden)
74
(Forbidden)
75
Setting number
Default
Adjust the horizontal swing airflow
00 Standard
direction.
01 Left half
(For horizontal swing equipped
02 Right half
models)
Adjust the cool air trigger tempera-
00 Standard
ture. To lower the trigger tem-
01 Adjust (1)
perature, use setting 01. To raise the
02 Adjust (2)
trigger temperature, use setting 02.
Adjust the heat air trigger tempera-
00 Standard
ture. To lower the trigger temperature
01 Adjust (1)
by 6 degrees C, use setting 01. To
02 Adjust (2)
lower the trigger temperature by 4
degrees C, use setting 02. To raise
03 Adjust (3)
the trigger temperature, use setting
03.
00 Enable
Enable or disable automatic system
restart after a power outage.
01 Disable
00 Super low
Restrain the cold airflow with making
Follow the
the airflow lower when starting heat-
setting on
ing operation. To correspond to the
01
the remote
ventilation, set to 01.
controller
Allow an external controller to start
00 Start/Stop
or stop the system, or to perform an
Emergency
01
emergency stop.
stop
* If an emergency stop is performed
from an external controller, all re-
frigerant systems will be disabled.
* If forced stop is set, indoor unit
02 Forced stop
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
00 All
Change the target for reporting
errors. Errors can either be reported
Display only on
in all locations, or only on the central
01
central remote
remote controller.
controller
When set to 01, the fan stops when
Follow the
the thermostat is OFF in cooling
setting on
00
operation. Connection of the wired
the remote
remote controller (2-wire type or
controller
3-wire type) and switching its therm-
01 Stop
istor are necessary.
Forced ther-
00
mostat off
01
02
03
Setting is required when connecting
04
a refrigerant-leak detecting device.
(Forbidden)
05
(only for J-IIIL series)
06
07
08
Refrigerant
09
leak detection
00
00
Single
Switch the setting method of
setpoint auto
auto mode to single or dual
00
mode
(cooling/heating).
(traditional)
For heat pump systems, it is
Dual setpoint
necessary to set the master indoor
01
unit (by wired remote controller).
auto mode
00 0°C
01 0.5°C
02 1.0°C
03 1.5°C
Choose the minimum temperature
between cooling and heating
04 2.0°C
settings (deadband) for Dual
05 2.5°C
setpoint auto mode (set in No. 68).
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C
00
00
00
00
00
Details