AirStage AB A030GTEH Series Kurulum Kılavuzu - Sayfa 7

Klima AirStage AB A030GTEH Series için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. AirStage AB A030GTEH Series 16 sayfaları.

Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to
tighten the fl are nut correctly.
When the fl are nut is tightened properly by your hand, hold the body side coupling with a
separate spanner, then tighten with a torque wrench.
Torque wrench
Indoor unit pipe
(Body side)
Flare nut [mm (in)]
6.35 (1/4) dia.
9.52 (3/8) dia.
12.70 (1/2) dia.
15.88 (5/8) dia.
19.05 (3/4) dia.
Be sure to install the pipe against the port on the indoor unit and the outdoor unit
correctly. If the centering is improper, the fl are nut cannot tightened smoothly. If the
fl are nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before
connecting the connection pipe.
Do not use mineral oil on fl ared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.

4.4. Installing heat insulation

Install the heat insulation material after performing a refrigerant leak check (see the Instal-
lation Manual for the outdoor unit for details).
Coupler heat insulation
• Insulate by the coupler heat insulation (Accessories) around the gas pipe and liquid
pipe of indoor side.
• After installing the coupler heat insulation, wrap both end with vinyl tape so that there is
no gap.
• After affi xing the coupler heat insulation, secure it with 2 cable ties, one on each end of
the insulation.
• Make sure that the Cable ties overlap the heat insulation pipe.
And fi nally fi x connection pipe (Liquid) to connection pipe (Gas) by rolling vinyl tape over
coupler heat insulation (Gas) and coupler heat insulation (Liquid).
After checking for gas leaks (refer to the Installation Manual of the outdoor unit),
perform this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to
do so may cause water leaks.
CAUTION
Tighten with 2 wrenches.
Holding wrench
Flare nut
Connection pipe
Tightening torque [N·m (kgf·cm)]
16 to 18 (160 to 180)
32 to 42 (320 to 420)
49 to 61 (490 to 610)
63 to 75 (630 to 750)
90 to 110 (900 to 1,100)
CAUTION
CAUTION
Coupler heat insulation (Large)
(Accessories)
Indoor unit
Coupler heat insulation (Small)
(Accessories)
Indoor unit
Cable tie (Large)
(Accessories)
Indoor unit
* When using an Auxiliary pipe (Accessories), make sure that 2 pieces of fasteners used
is insulated in the same way.

5. INSTALLING DRAIN PIPES

Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride)
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain pipe that matches the size of the drain hose.
• Do not perform a rise, trap and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.
• Always heat insulate (8 mm or over thick) the indoor side of the drain pipe.
Drain pipe
GOOD
Arrange the drain pipe lower
than this portion.
GOOD
Supporter
PROHIBITED
Lifted up
Connection pipe (Gas)
Connection pipe (Small) (Liquid)
Cable tie (Extra large)*
(Accessories)
No gap
Coupler heat insulation
Connection pipe (Gas)
Connection pipe (Liquid)
Vinyl tape
O.D.
32 mm (VP25)
Drain pipe
1.5 to 2 m
End in water
Wave
En-6