AirStage ABUA12TLAV Kurulum Kılavuzu - Sayfa 4

Klima AirStage ABUA12TLAV için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. AirStage ABUA12TLAV 17 sayfaları. Indoor unit

AirStage ABUA12TLAV Kurulum Kılavuzu
Name and Shape
Drain hose insulation
VT wire
Insulation (Pipe)
Silencer pipe
] 1

2.4. Optional parts

Description
Auxiliary pipe
UTY-XWZXZC
UTY-XWZXZB
External connect kit
UTY-XWZXZD
UTY-XWZXZE
1

2.5. About unit of the length

All Fujitsu General products are manufactured to metric units and tolerances. United
States customary units are provided for reference only. In cases where exact dimensions
and tolerances are required, always refer to metric units.

3. INSTALLATION WORK

Correct initial installation location is important because it is diffi cult to move unit after it is
installed.
] 1

3.1. Selecting an installation location

Decide the mounting position together with the customer as follows.
Select installation locations that can properly support the weight of the indoor unit.
Install the units securely so that they do not topple or fall.
Do not install the indoor unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts,
causing the parts to fail or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit
to leak water.
• Area that generates substances that adversely affect the equipment, such as
sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed
joints to corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon fi bers or
fl ammable dust, or volatile infl ammables such as paint thinner or gasoline. If gas
leaks and settles around the unit, it can cause a fi re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals,
growing plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or fl ammable gas.
Install the unit where drainage does not cause any trouble.
En-3
Q'ty
Application
Adhesive type
3-15/16 × 8-11/16 in.
1
(100 × 220 mm)
For fi xing the drain hose
L 11 in. (280 mm)
1
Adhesive type
6-5/16 × 4-5/16 in.
1
(160 × 110 mm)
Connect the silencer pipe to the small
(liquid) pipe.
1
Model No.
Application
For indoor side pipe joint
(For AB18, AB24)
9374714025
For output function
(Output terminal / CNB01)
For control input function
(Apply voltage terminal / CNA01)
For control input function
(Dry contact terminal / CNA02)
For forced thermostat off function
UTY-XWZXZ7
(Apply voltage terminal / CNA03)
For forced thermostat off function
(Dry contact terminal / CNA04)
WARNING
CAUTION
Install the indoor unit, power supply cable, transmission cable, and remote controller
cable at least 40 in. (1 m) away from a television or radio receivers. The purpose
of this is to prevent TV reception interference or radio noise. (Even if they are
installed more than 40 in. (1 m) apart, you could still receive noise under some signal
conditions.)
If children under 10 years old may approach the unit, take preventive measures so
that they cannot reach the unit.
Take precautions to prevent the unit from falling.
(1) Install the indoor unit on a place having a sufficient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(5) Install the unit where the connection pipe can be easily installed.
(6) Install the unit where the drain pipe can be easily installed.
(7) Install the unit where noise and vibrations are not amplifi ed.
(8) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the fi lter can be removed.
(9) Do not install the unit where it will be exposed to direct sunlight.
] 1

3.2. Installation dimension

Floor console
Left
12 (300)
or more
Under ceiling
Left
6 (150)
or more
91 (2300)
CAUTION
Right
Unit: in. (mm)
12 (300)
or more
Ceiling
Right
Indoor unit
12 (300)
or more
Ceiling
1 (20)
or more
or more
Floor
Unit: in. (mm)