AirStage ABUA14TLAV Kurulum Kılavuzu - Sayfa 9
Klima AirStage ABUA14TLAV için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. AirStage ABUA14TLAV 17 sayfaları. Indoor unit
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cables to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 2 in. (50 mm) or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of
the PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral
devices.
• Cut power (breaker) off.
• Touch metal part of the indoor unit for more than 10 seconds to discharge static
electricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.
] 1
6.1. Electrical requirement
Voltage rating
Operating range
• Select the power cable type and size in accordance with relevant local and national
regulations.
• Specifi cations for local wiring power cord and branch wiring are in compliance with local
code.
• Select the correct cable type and size according to the country or region's regulations.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Refer to the table for the breaker specifi cations of each installation condition. Perform the
power crossover wiring within the range of the same refrigerant system. When the crossover
wiring is done, make a connection for indoor units to satisfy conditions A and B below.
A. Current breaker requirements
Model
MCA
ABUA12TLAV
0.40 A
ABUA14TLAV
0.43 A
ABUA18TLAV
0.71 A
ABUA24TLAV
0.93 A
MCA: Minimum Circuit Ampacity
MAX. CKT. BKR : Maximum Circuit Breaker
When the power crossover wiring is done, make it so that the total of the MCA of the
connected RB units and indoor units does not exceed the 11 A. For RB unit MCA, refer to
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add
breakers or use a breaker with a greater capacity.
B. Ground Fault Equipment Breaker requirements
Breaker capacity
30 mA, 0.1 sec or less
100 mA, 0.1 sec or less
* Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
** If the total number of units connected to the breaker exceeds 36, either add a 30mA
breaker, or use breakers with a greater capacity.
6.1.1. Cable specifi cations
Follow the specifi cations below for the power supply, transmission and remote controller
cable.
Recommended
cable size
22 AWG
Transmission cable
(0.33 mm²)
22 AWG
Remote controller cable
(0.33 mm²) to 16
(2-wire type)
AWG (1.25mm²)
Remote controller cable
22 AWG
(3-wire type)
(0.33 mm²)
CAUTION
208/230 V
187 to 253 V
MAX. CKT. BKR (Fuse capacity)
15 A
* Maximum connectable "indoor units"
or "indoor units + RB units"
36 or less **
37 to 90
Cable type
Remark
22 AWG LEVEL 4
(NEMA) non-polar
LONWORKS
2 core, twisted pair
compatible cable
solid core diameter
0.026 in. (0.65 mm)
Sheathed
Non polar 2 core
PVC cable
Sheathed
Polar 3 core
PVC cable
] 1
6.2. Wiring method
EXAMPLE
Outdoor unit or RB unit *1
Transmission
Indoor unit
Remote
Transmission
control
Power supply
*2
Breaker2
Breaker1
Remote controller
(Master)
Power supply
Breaker shall be located in sight from and readily accessible from all indoor units.
*1: When connecting to the Heat Recovery System, refer to the installation manual of the
RB unit.
*2: When connecting the 2-wire type remote controller, Y3 is not used.
(Crossover wiring of power supply)
Indoor unit
Power supply
Power supply
Pull box
Breaker2
Breaker1
Power supply
Disconnect switch shall be installed between indoor unit and pull box.
1
6.3. Unit wiring
Before attaching the cable to terminal block.
6.3.1. Power supply cable
Adjust the length of power supply cable to avoid excessive tension with referring fi gure
below.
Earth
(Ground)
wire
3-1/8 in.
(80mm)
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after looping
it around the end of the cable.
(2) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not fi x 2 power supply cables with 1 screw.
Strip 1 in.
(25 mm)
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
Breaker 1: Ground Fault Equipment
Breaker (GFEB)
Breaker 2: Maximum Circuit Breaker
(MAX. CKT. BKR)
Indoor unit
Indoor unit
*2
Breaker2
Breaker2
Breaker1
Breaker1
Remote controller
Remote controller
(Slave)
Indoor unit
Indoor unit
Power supply
Pull box
: Disconnect switch
Conduit
3-1/8 in.
connector
(80mm)
Loop
Screw with
special washer
Cable end (Loop)
Cable
*2
En-8