AirStage ASUB18RLAV Kurulum Kılavuzu - Sayfa 13
Klima AirStage ASUB18RLAV için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. AirStage ASUB18RLAV 17 sayfaları. Indoor unit (wall mounted type)
Ayrıca AirStage ASUB18RLAV için: Kullanım Kılavuzu (8 sayfalar)
] 1
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Fig. B
Confusion
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP SW SET 3 SW1, 2, referring to the Table B.
ON
OFF
SW SW SW SW
1
2
3
4
Table B
A (Factory setting)
DIP SW
OFF
SET 3 SW1
DIP SW
OFF
SET 3 SW2
Code change
A
B
C
D
A
B
C
D
Dip switch
"SET 3"
Custom code
B
C
ON
OFF
OFF
ON
] 1
7.3. Function setting
Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Filter
indicator
11
interval
Filter
indicator
13
action
Horizontal
swing
24
airfl ow
direction
Cool air
D
tem-
30
perature
ON
trigger
ON
Heat air
tem-
31
perature
trigger
Auto
40
restart
External
46
control
Error report
47
target
WARNING
Setting
Default
number
○
00
Default
Adjust the fi lter cleaning interval notifi -
cation. If the notifi cation is too early,
01
Longer
change to setting 01. If the notifi cation
is too late, change to setting 02.
02
Shorter
○
00
Enable
01
Disable
Enable or disable the fi lter indicator.
Display
Setting 02 is for use with a central
only on
remote controller.
02
central
remote
controller
○
00
Default
Adjust the horizontal swing airfl ow
direction.
01
Left half
(For horizontal swing equipped mod-
els)
02
Right half
○
00
Default
Adjust the cool air trigger tempera-
ture. To lower the trigger temperature,
01 Adjust (1)
use setting 01. To raise the trigger
temperature, use setting 02.
02 Adjust (2)
○
Adjust the heat air trigger temperature.
00
Default
To lower the trigger temperature by
11 degrees F (6 degrees C), use setting
01 Adjust (1)
01. To lower the trigger temperature by
02 Adjust (2)
7 degrees F (4 degrees C), use setting
02. To raise the trigger temperature,
03 Adjust (3)
use setting 03.
00
Enable
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency function
such as for power failure etc.
○
Do not start and stop the indoor unit
01
Disable
by this function in normal operation.
Be sure to operate by the control unit,
converter or external input device.
Allow an external controller to start
○
00 Start/Stop
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all refrig-
Emergen-
01
erant systems will be disabled.
cy stop
* If forced stop is set, indoor unit stops
by the input to the external input
terminals, and Start/Stop by a remote
Forced
02
controller is restricted.
Stop
○
00
All
Change the target for reporting er-
Display
rors. Errors can either be reported in
only on
all locations, or only on the central
01
central
remote controller.
remote
controller
Details
En-12